3.2 Trouble shooting
3.2.1 E1, E2 ---IDU Room temperature sensor and/or coil temperature sensor failure.
Start
Display E1or E2
Re-connect
Is the sensor well
connected to PCB
Multi-meter check the
sensor, is it open or
short circuit?
Replace the sensor
No
Yes
Yes
Replace IDU PCB
The malfunction
eliminated?
End
E1/E2
disappear?
Yes
No
No
No
Yes
Air Conditioner Service Manual
32
Summary of Contents for 09CH-FIXED-A1
Page 7: ...MODEL 75 1 2 INDOOR UNIT Air Conditioner Service Manual OUTDOOR UNIT 6...
Page 8: ...Air Conditioner Service Manual MODEL 75 1 75 1 75 1 INDOOR UNIT OUTDOOR UNIT 7...
Page 9: ...Air Conditioner Service Manual MODEL 75 1 INDOOR UNIT OUTDOOR UNIT 8...
Page 36: ...Air Conditioner Service Manual SORVLRQ YLHZ DQG SDUWV OLVW RPLW 35...