![Trane Technologies DRV03113 Installation Manual Download Page 17](http://html1.mh-extra.com/html/trane-technologies/drv03113/drv03113_installation-manual_1150445017.webp)
BAS-SVN029C-EN
17
Table 6.
TR170 VFD drive parameters CGAM (continued)
Parameter Number
Parameter Description
CGAM Setting
Units
3-16
Reference 2 Source
No function (0)
—
3-17
Reference 3 Source
No function (0)
—
3-41
Ramp 1 Ramp Up Time
5
s
3-42
Ramp 1 Ramp Down Time
20
s
4-10
Motor Speed Direction
Clockwise (0)
—
4-12
Motor Speed Low Limit [Hz]
5/6
Hz
4-14
Motor Speed High Limit [Hz]
50/60
Hz
4-18
Current Limit
If p122 = 460V then 115 Else 110
%
5-12
Terminal 27 Digital Input
No operation (0)
—
5-40
Function Relay
Alarm (9)
—
6-10
Terminal 53 Low Voltage
1
V
6-14
Terminal 53 Low Ref./Feedb. Value
5/6
—
6-15
Terminal 53 High Ref./Feedb. Value
50/60
—
14-01
Switching Frequency
5
kHz
14-12
Function at Mains Imbalance
De-rate (3)
—
14-20
Reset Mode
Auto Reset x10 (10)
—
14-21
Automatic Restart Time
30
s
14-50
RFI Filter
Off (0)
—
Note:
*60 or 50Hz for Pueblo Production, 50Hz for Charmes production. Otherwise, set for maximum speed rating of motor/fan.
Copying Parameters to Multiple Drives
If you are installing multiple drives, the drive LCP (local control panel) can be used to copy
parameters from one drive to another. This method can save time and reduce errors.
U
Up
pllo
oa
ad
diin
ng
g D
Da
atta
a tto
o tth
he
e L
LC
CP
P
1. Go to 0-50 LCP copy.
2. Press O
OK
K.
3. Select A
Allll ffrro
om
m L
LC
CP
P.
4. Press O
OK
K.
A progress bar shows the uploading process
5. Press H
Ha
an
nd
d o
on
n to return to normal operation.
Remove the LCP from the configured drive and install it on the unconfigured drive.
D
Do
ow
wn
nllo
oa
ad
diin
ng
g D
Da
atta
a ffrro
om
m tth
he
e L
LC
CP
P
1. Go to 0-50 LCP copy
2. Press O
OK
K
3. Select A
Allll ffrro
om
m L
LC
CP
P
4. Press O
OK
K.
A progress bar shows the uploading process