Installing TR170 VFD and Components

Remove Trane TR170 drive from the box, verify the VFD model number, and complete the
following procedures.

Install the TR170 Drive

1. Attach the new drive heater, HTR16716, to the side of the new drive. If another drive is

present in the panel, the heater should be placed on the side of the drive that will not face the
other drive. The heater has adhesive pre-applied to one side. Remove the protective film from
the heater and press it against the side of the drive.

2. Hold the drive up to the back plate and mark the mounting hole locations on the backplate.

N

No

otte

e:: The Trane TR170 drive has a mounting hole pattern different than the original drive.

3. Drill a 3/16" hole at each marked location. Be careful to protect other electrical components

from metal shavings and clean all metal shavings from the enclosure when drilling is
completed.

4. Line up the TR170 on the mounting hole-pattern and fasten the drive with the fasteners

retained from the original drive to the back panel.

Wire the Power Supply and Controls to the TR170

The TR1 and TR170 have the same connection point numbers, however, a four-compressor unit
or circuit 1 of a three-compressor unit requires an additional relay. These units will require the
unit schematics to be marked up or replaced. Schematics document numbers may be found in

“Wiring Diagram Matrix,” p. 21

. Print a copy from e-Library (if accessible) or contact the local

Trane representative to obtain a copy.

1. Reconnect power supply wires to VFD connection points 91, 92, 93, 95 (L1, L2, L3, GND

respectively) and output power wires to VFD connection points 96, 97, 98, 99 (T1, T2, T3, GND
respectively).

2. Reconnect all control wires to the TR170 VFD according to the connection point numbers

noted during TR1 removal. The TR1 and TR170 have the same connection point numbers.
(See the “Typical Control Wires” table in

“Remove the Control Wiring ,” p. 9

for common

control wires and their connection point numbers.)

3. Connect the new drive blanket heater wiring to 1TB7-3,4 or 2TB7-3,4.

Installing the Drive On a Four-Compressor Unit or Circuit 1 of a Three-Compressor Unit
(RTAC)

If you are installing the drive on a four-compressor unit or circuit 1 of a three-compressor unit, an
addition relay is required.

1. Mount this relay and base on the controls backplate.

2. Label the relay 1K9 if installed in control panel 1 or 2K9 if installed in control panel 2.

3. Make the wiring modifications presented in the following table:

Table 3. Intermediate relay wiring

Control Panel 1

Wire Number

Description of New
Function

Original Connections

New Connections

151A

+24 VDC

1U28-12 to 1TB6-6

1U28-12 to 1K9-1

152A

Digital Input (RUN)

1U28-18 to 1TB6-7

1U28-18 to 1K9-2

151B

+24 VDC

1U29-12 to 1TB6-6

1U29-12 to 1K9-3

152B

Digital Input (RUN)

1U29-18 to 1TB6-7

1U29-18 to 1K9-4

151C

Control Power Hot

1U15-J2-12 to 1TB6-6

1U15-J2-12 to 1TB5-3

(Node 62)

Summary of Contents for DRV03113

Page 1: ...ly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stic...

Page 2: ...our customers and the air conditioning industry All technicians who handle refrigerants must be certified according to local rules For the USA the Federal Clean Air Act Section 608 sets forth the requ...

Page 3: ...iz ze ed d e el le ec ct tr ri ic ca al l c co on nt ta ac ct t a ar rc c o or r f fl la as sh h t te ec ch hn ni ic ci ia an ns s M MU US ST T p pu ut t o on n a al ll l P PP PE E i in n a ac cc co...

Page 4: ...nstall the TR170 Drive 11 Wire the Power Supply and Controls to the TR170 11 Installing the Drive On a Four Compressor Unit or Circuit 1 of a Three Compressor Unit RTAC 11 Set the VFD Programming Para...

Page 5: ...an drives The number of drives will match the number of compressors For example a three compressor RTAC will have three condenser fan drives The installation instructions in this manual are divided in...

Page 6: ...losure for Intellipak II CGAM and RTAC units as shown in the following figures 2 Identify the correct VFD for replacement The IntelliPak II rooftops with low ambient option always have two condenser f...

Page 7: ...iguration Figure 4 Typical CGAM 70 ton panel illustration and low ambient option VFD location Low Ambient Option Condenser Fan VFD R Re em mo ov vi in ng g t th he e E Ex xi is st ti in ng g V VF FD D...

Page 8: ...guration Figure 6 Typical RTAC 200 ton panel illustration and low ambient option VFD location Low Ambient Option Condenser Fan VFD R Re em mo ov vi in ng g t th he e E Ex xi is st ti in ng g V VF FD D...

Page 9: ...P PA A 7 70 0E E t th ha at t a al ll l c ca ap pa ac ci it to or rs s h ha av ve e d di is sc ch ha ar rg ge ed d F Fo or r a ad dd di it ti io on na al l i in nf fo or rm ma at ti io on n r re eg ga...

Page 10: ...e e u un ni it t m mu us st t b be e c ca ap pa ab bl le e o of f s su up pp po or rt ti in ng g t th he e e en nt ti ir re e w we ei ig gh ht t o of f t th he e u un ni it t L Li if ft ti in ng g c c...

Page 11: ...may be found in Wiring Diagram Matrix p 21 Print a copy from e Library if accessible or contact the local Trane representative to obtain a copy 1 Reconnect power supply wires to VFD connection points...

Page 12: ...Ar rc c F Fl la as sh h R Re eq qu ui ir re ed d F Fa ai il lu ur re e t to o w we ea ar r a ap pp pr ro op pr ri ia at te e P PP PE E c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r...

Page 13: ...erify Parameter 5 12 is set per Table 4 p 14 Table 5 p 15 and Table 6 p 16 for the given Product you are installing the drive into parameter 5 12 will be set to either Coast Inverse or No Function dep...

Page 14: ...s to all parameters ALWAYS use this method Table 4 TR170 VFD drive parameter RTAC Parameter Number Parameter Description RTAC Setting Units 0 03 Regional Settings North America for 60 Hz International...

Page 15: ...parameters Ipak II Parameter Number Parameter Description Ipak II Setting Units 0 03 Regional Settings North America for 60 Hz International for 50 Hz 0 06 Grid Type Depends on Grid Type 0 40 Hand on...

Page 16: ...ing table defines the complete set of parameters for the TR170 VFD drives used in condenser fan applications on CGAM products Table 6 TR170 VFD drive parameters CGAM Parameter Number Parameter Descrip...

Page 17: ...oduction 50Hz for Charmes production Otherwise set for maximum speed rating of motor fan Copying Parameters to Multiple Drives If you are installing multiple drives the drive LCP local control panel c...

Page 18: ...sources TGE Online Help Tracer Ensemble Online Help Tracer Ensemble User Guide BAS SVU09 Tracer SC Online Help Tracer TU Online Help I In ns st ta al ll li in ng g T TR R1 17 70 0 V VF FD D a an nd d...

Page 19: ...plications an additional heater blanket as well as applicable wiring and accessories may also need to be installed to make heater blankets operational The following two diagrams show installation of h...

Page 20: ...in IPak II 460 volt option See Wire the Power Supply and Controls to the TR170 p 11 for the procedure used to wire the power supply and controls to the TR170 I In ns st ta al ll li in ng g T TR R1 17...

Page 21: ...150 TON WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT 2313 0850 SCHEMATIC POWER 120 150 TON WITH SUPPLY AND EXHAUST OR RETURN VFD W LOW AMBIENT 2313 0839 SCHEMATIC POWER 90 105 TON STANDARD WITH LOW...

Page 22: ...py Table 8 TR170 VFD CGAM wiring schematics and connection diagrams Wiring Diagram Number Description 2309 2075 SCHEMATIC CGAM S V W N No ot te e Wiring diagrams are available via e Library if accessi...

Page 23: ...BAS SVN029C EN 23 N No ot te es s...

Page 24: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications w...

Reviews: