![Trane Technologies DRV03113 Installation Manual Download Page 13](http://html1.mh-extra.com/html/trane-technologies/drv03113/drv03113_installation-manual_1150445013.webp)
BAS-SVN029C-EN
13
5.
Cut off the main supply and wait until the display turns off.
6.
Reconnect the main supply.
The frequency converter is now reset.
7. Ensure parameter 14–22 Operation Mode has reverted back to “Normal Operation”.
N
No
otte
ess::
•
Step 5 resets the drive to the default factory settings. The program parameters
listed in
and
will need to be verified or
changed as described in the previous Modify Parameters procedure.
•
Some of the parameters listed in the Table are motor specific. Due to various
motors and efficiencies available, use only the values stamped on the specific
motor nameplate. Do not use the Unit nameplate values.
•
A backup copy of the current setup may be saved to the LCP before changing
parameters or resetting the drive. See LCP Copy in the VFD Operating Instructions
for details.
Modify Parameters
Please refer to BAS-SVP16*-EN (
TR150 and TR170 Programming Guide
), or the most recent
version, for complete programming information.
N
No
otte
ess::
•
Pressing the “MENU” button once will enter the drive parameter wizard. The
parameter wizard does not access all the required parameters.
•
To access ALL parameters, press the “MENU” button twice.
•
The parameters are set by different levels. Click OK to access Level 1 and Level 2.
•
The default setting for Parameter 5-12 is Coast inverse which will cause a drive error
on Products that do not need that function. Verify Parameter 5-12 is set per
and
for the given Product you are installing the drive
into (parameter 5-12 will be set to either Coast Inverse or No Function depending on
your Product). Products that utilize the Coast inverse function will have a control wire
going to terminal 27 on the drive.
Perform the following steps to modify each parameter:
1. On the first power up of the drive, a parameter wizard may appear. Press the B
Ba
acckk button to
leave the wizard screen.
2. Press the M
Ma
aiin
n M
Me
en
nu
u button.
(Press the B
Ba
acckk button if the main menu does not display.)
3. Use the U
Up
p and D
Do
ow
wn
n buttons to find the parameter menu group (first part of parameter
number).
4. Press O
OK
K.
5. Use the U
Up
p and D
Do
ow
wn
n buttons to select the correct parameter sub-group, indicated by the
first digit of the second part of the parameter number.
6. Press O
OK
K.
7. Use the U
Up
p and D
Do
ow
wn
n buttons to select the specific parameter.
8. Press O
OK
K.
9. Use the navigation buttons to move to a different digit within a parameter setting.
The highlighted area indicates the digit selected for modification.
10. Use the U
Up
p and D
Do
ow
wn
n buttons to adjust the digit.
11. Press C
Ca
an
ncce
ell to disregard the change, or press O
OK
K to accept the change and enter the new
setting.
12. Repeat steps 1 through 11 for each menu selection setting in the parameters table.
13. After verifying that the VFD(s) are operating properly, press the STOP key at the Human