background image

Removal and Installation

COM-SVN003B-EN

15 

Leak Detection

Pressure Testing

Use industry-standard and EPA-accepted techniques 
for testing.

Pressure tests must be performed by qualified 
personnel.

Use tools especially designed for leak testing.

Do not exceed the high-side and low-side pressures 
listed on the unit nameplate.

If no test pressure value is listed on the nameplate of 
the unit, a pressure of no more than 150 psig is 
acceptable.

The CSHW compressor has an internal check valve. 
When pressurizing the system, it is important to never 
allow the low side pressure to exceed the high side 
pressure by more than 5 bar (72 psig). Greater 
pressure differential could result in compressor 
damage. Also slowly raise the pressure over a 
2-minute time period to allow sufficient time for 
internal pressures in the compressor to equalize.

Pressure decay testing can be used to check for gross 
leaks but will not be able to detect the location of a leak.

After pressurizing the system use an R-410A leak 
detection device to detect and locate leaks.

Vacuum Testing and Evacuation

Use the procedure as described in the unit Installation, 
Operation, and Maintenance manual.

If no other information is available, use the following 
information.

Ensure that there is no voltage being applied to the 
compressor terminals.

Evacuate the unit to 500 microns.

Hold vacuum for 30 minutes.

Rapid pressure rise indicates a leak; locate and repair 
the leak.

Slow pressure rise indicates one of two possibilities:

A small leak, indicated by a continuous rise in 
pressure.

Moisture in the system, indicated by a slow rise in 
pressure and leveling-out at a pressure equivalent 
to the moisture level. If this occurs, break the 

WARNING

Hazard of Explosion!

Failure to follow instructions below could result in 
death or serious injury or equipment or property-only 
damage. Use only dry nitrogen with a pressure 
regulator for pressurizing unit. Do not use acetylene, 
oxygen or compressed air or mixtures containing them 
for pressure testing. Do not use mixtures of a hydrogen 
containing refrigerant and air above atmospheric 
pressure for pressure testing as they may become 
flammable and could result in an explosion. Refrigerant, 
when used as a trace gas should only be mixed with dry 
nitrogen for pressurizing units. 

WARNING

Hazardous Pressures!

When using dry nitrogen cylinders for pressurizing units 
for leak testing, always provide a pressure regulator on 
the cylinder to prevent excessively high unit pressures. 
Never pressurize unit above the maximum 
recommended unit test pressure as specified in 
applicable unit literature. Failure to properly regulate 
pressure could result in a violent explosion, which could 
result in death or serious injury or equipment or 
property-only-damage. See maximum recommended 
unit test pressure below. 

NOTICE

Overpressure Damage!

Failure to follow these instructions could result in 
compressor damage. Do not pressurize the low side of 
the compressor by more than  5 bar  (72 psig)  higher 
than the high side of the compressor within less than 
two minutes.

NOTICE

Compressor Motor Damage!

Failure to follow these instructions could cause 
compressor motor damage. Never use the compressor 
as a vacuum pump. Never meg-ohm test or apply 
power to the compressor while it is in a vacuum.

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors 
before servicing could result in death or serious injury. 
Disconnect all electric power, including remote 
disconnects and discharge all motor start/run 
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be 
inadvertently energized. Verify with an appropriate 
voltmeter that all capacitors have discharged. 

For additional information regarding the safe discharge 
of capacitors, see PROD-SVB06*-EN. 

Summary of Contents for CSHW047

Page 1: ...ing up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqual...

Page 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Page 3: ...hould only be mixed with dry nitrogen for pressurizing units Failure to follow these instructions could result in death or serious injury or equipment or property only damage WARNING Hazardous Service...

Page 4: ...rmission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Page 5: ...8 Pre Installation Inspections 9 Repair Recommendations 9 Mechanical Failure 10 Electrical Failure 10 Two Types of Motor Failures 10 Removal and Installation 11 Removal 11 Compressor Replacement Tand...

Page 6: ...1 step Unloading with solenoid not energized Digit 10 Design Sequence Factory Assigned Digit 11 Motor Protection Type 0 Internal Line Break Digit 12 Compressor Connections Variation 0 Standard Compres...

Page 7: ...ion Some conditions will result in oil levels below the sight glass Off After several minutes theoil levels should be the same in each compressor and should be visible in the sightglass This is the be...

Page 8: ...system charge exceeds 3 pounds per ton crankcase heaters are required If required heaters must be energized for a minimum of eight hours prior to starting the compressor to insure that liquid refrige...

Page 9: ...ngs may not be of the same length Adjust as necessary for even unit lift Table 2 Compressor weight without oil charge Model Weight lb Weight kg CSHW 047 050 052 056 83 8 38 CSHW 052 2 86 39 CSHW 058 0...

Page 10: ...rs using an acid test kit Use Trane Part Numbers CHM00414 and 45006 Two Types of Motor Failures Light If oil test kit is negative and oil is only slightly discolored treat in the same manner as a mech...

Page 11: ...compressor Cut the refrigerant lines in a convenient location that allows reassembly with slip couplings Then unbraze the line from the compressor and reuse it when the replacement is installed WARNIN...

Page 12: ...and shipping For single applications this equalizer port will need to be brazed shut with a 1 125 tube and cap If the replacement compressor requires a full oil charge then the compressor can be tipp...

Page 13: ...of the refrigerant system iv Reinsert the tube into the compressor connection If the tubing does not stay fully inserted it must be restrained to prevent it from backing out of the compressor connecti...

Page 14: ...order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions U...

Page 15: ...equipment or property only damage Use only dry nitrogen with a pressure regulator for pressurizing unit Do not use acetylene oxygen or compressed air or mixtures containing them for pressure testing D...

Page 16: ...ng the evaporator Verification Before Start Up Follow the instructions in the unit Installation Operation and Maintenance manual If there are no instructions available use these guidelines Before star...

Page 17: ...ly when the compressor is operating Do not overcharge the unit Recommended system full load superheats unless specified differently in the unit Installation Operation and Maintenance manual is 16 F 20...

Page 18: ...eat sub cooling oil sump superheat voltage and amperage Check all of the following on a regular basis System operating conditions System refrigerant charge level Oil levels and oil color Check electri...

Page 19: ...mum of eight hours or it is defective Mechanical damage to the compressor has occurred Check compressor amperage It may also trip the compressor motor protection module or other unit electrical protec...

Page 20: ...on Operation and Maintenance manual for possible diagnostics codes and corrective action Also check for Defective unit controls maximum 12 starts per hour Compressors cycling on safety controls Unit o...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: