background image

General Information

10

 COM-SVN003B-EN

Mechanical Failure

Replace only the failed compressor in a tandem or trio set.

Important:

On tandem or trio assemblies, the suction 
and discharge lines must NOT be modified, 
except for the use of slip joint couplings. 
Other modification may cause oil return 
issues and lead to compressor failure. Cut 
the lines in a convenient place, remove the 
compressor, and then unbraze the lines 
from the compressor. On re-installation, 
reinstall lines to compressor and 
reassemble the cut lines utilizing a slip 
coupling. 

Minimize system and compressor open times to avoid 
excessive moisture absorption by the POE oil. Maximum 
suggested open time is 15 minutes.

Drain and replace oil in all the non-failed compressors.

The CSHW compressor has an oil drain with a Schrader

®

 

valve that can be used to remove the oil (see 

Figure 2, p. 9

).

Replace unit liquid line filter-drier. This is a very important 
part of controlling moisture in R-410A POE oil systems.

Reuse the compressors mounting isolators or mounting 
spacers that are used with the existing compressor 
assembly. 

Braze the compressor into the system. Compressor 
connections are copper-plated steel. Use BAg-28, 40% 
silver, with paste flux to make the copper tube connections 
to the compressor.

Proceed with the following as described in the following 
sections:

“Leak Detection,” p. 15

“Vacuum Testing and Evacuation,” p. 15

“Charging the System,” p. 16

“Verification Before Start-Up,” p. 16

Electrical Failure

Follow the mechanical failure guidelines. In addition to the 
Mechanical Failure Guidelines, check for acid in the 
system.

Test the acid condition of the oil in the compressors using 
an acid test kit. Use Trane Part Numbers CHM00414 and 
45006.

Two Types of Motor Failures

Light

 - If oil test kit is negative and oil is only slightly 

discolored, treat in the same manner as a mechanical 
failure.

Severe

 - If oil test kit is positive with strong pungent odor 

and dark oil, drain and replace oil in all of the non-failed 
compressors.

Reuse the compressor mounting isolators or mounting 
spacers that are used with the existing compressor 
assembly. 

This type of failure requires changing both the suction and 
liquid line filter-driers. Use replaceable filter-drier cores to 
facilitate changing filter-driers, if required.

Install the suction filters no closer than the distance listed 
in the following table. The distance is measured from the 
centerline of the suction inlet tee.

1. Use acid removal type filter-drier cores in both the 

suction filter and liquid line filter drier.

2. Change when the pressure drop exceeds 4 psig.

Test oil after 24 hours of operation. Change filter-drier 
again if required. If oil is still acid, drain and replace oil in 
all the non-failed compressors.

After system is clean, test kit indicates okay, remove the 
suction clean up filter-drier and replace the liquid line drier 
with standard filter drier cores.

WARNING

Hazard of Explosion!

Failure to follow instructions below could result in 
death or serious injury or equipment or property-only 
damage. Use only dry nitrogen with a pressure 
regulator for pressurizing unit. Do not use acetylene, 
oxygen or compressed air or mixtures containing them 
for pressure testing. Do not use mixtures of a hydrogen 
containing refrigerant and air above atmospheric 
pressure for pressure testing as they may become 
flammable and could result in an explosion. Refrigerant, 
when used as a trace gas should only be mixed with dry 
nitrogen for pressurizing units.

Summary of Contents for CSHW047

Page 1: ...ing up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqual...

Page 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Page 3: ...hould only be mixed with dry nitrogen for pressurizing units Failure to follow these instructions could result in death or serious injury or equipment or property only damage WARNING Hazardous Service...

Page 4: ...rmission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Page 5: ...8 Pre Installation Inspections 9 Repair Recommendations 9 Mechanical Failure 10 Electrical Failure 10 Two Types of Motor Failures 10 Removal and Installation 11 Removal 11 Compressor Replacement Tand...

Page 6: ...1 step Unloading with solenoid not energized Digit 10 Design Sequence Factory Assigned Digit 11 Motor Protection Type 0 Internal Line Break Digit 12 Compressor Connections Variation 0 Standard Compres...

Page 7: ...ion Some conditions will result in oil levels below the sight glass Off After several minutes theoil levels should be the same in each compressor and should be visible in the sightglass This is the be...

Page 8: ...system charge exceeds 3 pounds per ton crankcase heaters are required If required heaters must be energized for a minimum of eight hours prior to starting the compressor to insure that liquid refrige...

Page 9: ...ngs may not be of the same length Adjust as necessary for even unit lift Table 2 Compressor weight without oil charge Model Weight lb Weight kg CSHW 047 050 052 056 83 8 38 CSHW 052 2 86 39 CSHW 058 0...

Page 10: ...rs using an acid test kit Use Trane Part Numbers CHM00414 and 45006 Two Types of Motor Failures Light If oil test kit is negative and oil is only slightly discolored treat in the same manner as a mech...

Page 11: ...compressor Cut the refrigerant lines in a convenient location that allows reassembly with slip couplings Then unbraze the line from the compressor and reuse it when the replacement is installed WARNIN...

Page 12: ...and shipping For single applications this equalizer port will need to be brazed shut with a 1 125 tube and cap If the replacement compressor requires a full oil charge then the compressor can be tipp...

Page 13: ...of the refrigerant system iv Reinsert the tube into the compressor connection If the tubing does not stay fully inserted it must be restrained to prevent it from backing out of the compressor connecti...

Page 14: ...order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions U...

Page 15: ...equipment or property only damage Use only dry nitrogen with a pressure regulator for pressurizing unit Do not use acetylene oxygen or compressed air or mixtures containing them for pressure testing D...

Page 16: ...ng the evaporator Verification Before Start Up Follow the instructions in the unit Installation Operation and Maintenance manual If there are no instructions available use these guidelines Before star...

Page 17: ...ly when the compressor is operating Do not overcharge the unit Recommended system full load superheats unless specified differently in the unit Installation Operation and Maintenance manual is 16 F 20...

Page 18: ...eat sub cooling oil sump superheat voltage and amperage Check all of the following on a regular basis System operating conditions System refrigerant charge level Oil levels and oil color Check electri...

Page 19: ...mum of eight hours or it is defective Mechanical damage to the compressor has occurred Check compressor amperage It may also trip the compressor motor protection module or other unit electrical protec...

Page 20: ...on Operation and Maintenance manual for possible diagnostics codes and corrective action Also check for Defective unit controls maximum 12 starts per hour Compressors cycling on safety controls Unit o...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: