background image

COM-SVN003B-EN

11 

Removal and Installation

Only qualified personnel should install or repair 
refrigeration systems. If you are not qualified, seek the 
services of qualified personnel. The steps listed below are 
not meant to be an exact step-by-step procedure, but are 
intended to identify procedures or precautions that may 
be unique to a Trane compressor and should be taken into 
account to properly and safely remove and install the 
compressor. Each installation has its unique set of 
circumstances which must be considered by the service 
technician to perform a safe and successful compressor 
replacement.

Removal

Prior to removing the compressor, open the unit 
disconnect and place a lock on the disconnect to 
prevent someone else from accidentally applying 
power to the unit while it is under repair. 

Completely recover the refrigerant from the refrigerant 
circuit being repaired. Do not release refrigerant to the 
atmosphere! Use Responsible Refrigerant Practices. If 
adding or removing refrigerant, the service technician 
must comply with all Federal, State, and local laws.

Before removing the electrical connections on the 
compressor, use a voltmeter to check for the absence 
of power on the compressor power terminals.

After confirming the absence of power, remove the 
electrical connections.

Remove and measure oil from failed compressor prior 
to compressor removal:

CSHW compressors have an oil drain valve (see 

Figure 2, p. 9

) that allows oil to be drained out of the 

compressor. After the refrigerant has been 
recovered, pressurize the system with nitrogen to 
help remove oil from the compressor.

Record the amount of oil removed from the failed 
compressor. The replacement compressor oil 
charge should be adjusted to ensure that the 
equivalent amount of oil remains in the unit.

Tip:

Before removing the existing tubing from the 
compressor, apply flux to the joint. This will aid in 
the flow of the braze material and help keep the 
joint clean for rebrazing. After fluxing, heat the joint 
evenly to slightly higher temperature than the 
melting temperature of the filler material. At this 
point, the two parts of the assembly should be 
easily separated.

Refrigerant Connection Removal

Single compressor—Cut the refrigerant lines in a 
convenient location that allows reassembly with slip 
couplings. Then, unbraze the line from the compressor 
and reuse it when the replacement is installed.

WARNING

Refrigerant under High Pressure!

Failure to follow instructions below could result in an 
explosion which could result in death or serious injury 
or equipment damage. System contains oil and 
refrigerant under high pressure. Recover refrigerant to 
relieve pressure before opening the system. See unit 
nameplate for refrigerant type. Do not use non-
approved refrigerants, refrigerant substitutes, or 
refrigerant additives. 

WARNING

Hazard of Explosion and Deadly Gases!

Failure to follow all proper refrigerant handling 
practices could result in death or serious injury. 
Never solder, braze or weld on refrigerant lines or any 
unit components that are above atmospheric pressure 
or where refrigerant may be present. Always remove 
refrigerant by following the guidelines established by 
the EPA Federal Clean Air Act or other state or local 
codes as appropriate. After refrigerant removal, use dry 
nitrogen to bring system back to atmospheric pressure 
before opening system for repairs. Mixtures of 
refrigerants and air under pressure may become 
combustible in the presence of an ignition source 
leading to an explosion. Excessive heat from soldering, 
brazing or welding with refrigerant vapors present can 
form highly toxic gases and extremely corrosive acids. 

WARNING

Pressurized Burning Fluid!

Failure to follow these instructions could result in death 
or serious injury. Before opening a system, you must 
remove refrigerant from both the high and low sides of 
the system. If the pressure is not removed from both 
sides of the system, pressure could still exist in the 
system. If a torch is used to unbraze the tubing the 
refrigerant and oil mixture could ignite.

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors 
before servicing could result in death or serious injury. 
Disconnect all electric power, including remote 
disconnects and discharge all motor start/run 
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be 
inadvertently energized. Verify with an appropriate 
voltmeter that all capacitors have discharged. 

For additional information regarding the safe discharge 
of capacitors, see PROD-SVB06*-EN.

Summary of Contents for CSHW047

Page 1: ...ing up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqual...

Page 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Page 3: ...hould only be mixed with dry nitrogen for pressurizing units Failure to follow these instructions could result in death or serious injury or equipment or property only damage WARNING Hazardous Service...

Page 4: ...rmission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Page 5: ...8 Pre Installation Inspections 9 Repair Recommendations 9 Mechanical Failure 10 Electrical Failure 10 Two Types of Motor Failures 10 Removal and Installation 11 Removal 11 Compressor Replacement Tand...

Page 6: ...1 step Unloading with solenoid not energized Digit 10 Design Sequence Factory Assigned Digit 11 Motor Protection Type 0 Internal Line Break Digit 12 Compressor Connections Variation 0 Standard Compres...

Page 7: ...ion Some conditions will result in oil levels below the sight glass Off After several minutes theoil levels should be the same in each compressor and should be visible in the sightglass This is the be...

Page 8: ...system charge exceeds 3 pounds per ton crankcase heaters are required If required heaters must be energized for a minimum of eight hours prior to starting the compressor to insure that liquid refrige...

Page 9: ...ngs may not be of the same length Adjust as necessary for even unit lift Table 2 Compressor weight without oil charge Model Weight lb Weight kg CSHW 047 050 052 056 83 8 38 CSHW 052 2 86 39 CSHW 058 0...

Page 10: ...rs using an acid test kit Use Trane Part Numbers CHM00414 and 45006 Two Types of Motor Failures Light If oil test kit is negative and oil is only slightly discolored treat in the same manner as a mech...

Page 11: ...compressor Cut the refrigerant lines in a convenient location that allows reassembly with slip couplings Then unbraze the line from the compressor and reuse it when the replacement is installed WARNIN...

Page 12: ...and shipping For single applications this equalizer port will need to be brazed shut with a 1 125 tube and cap If the replacement compressor requires a full oil charge then the compressor can be tipp...

Page 13: ...of the refrigerant system iv Reinsert the tube into the compressor connection If the tubing does not stay fully inserted it must be restrained to prevent it from backing out of the compressor connecti...

Page 14: ...order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions U...

Page 15: ...equipment or property only damage Use only dry nitrogen with a pressure regulator for pressurizing unit Do not use acetylene oxygen or compressed air or mixtures containing them for pressure testing D...

Page 16: ...ng the evaporator Verification Before Start Up Follow the instructions in the unit Installation Operation and Maintenance manual If there are no instructions available use these guidelines Before star...

Page 17: ...ly when the compressor is operating Do not overcharge the unit Recommended system full load superheats unless specified differently in the unit Installation Operation and Maintenance manual is 16 F 20...

Page 18: ...eat sub cooling oil sump superheat voltage and amperage Check all of the following on a regular basis System operating conditions System refrigerant charge level Oil levels and oil color Check electri...

Page 19: ...mum of eight hours or it is defective Mechanical damage to the compressor has occurred Check compressor amperage It may also trip the compressor motor protection module or other unit electrical protec...

Page 20: ...on Operation and Maintenance manual for possible diagnostics codes and corrective action Also check for Defective unit controls maximum 12 starts per hour Compressors cycling on safety controls Unit o...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: