Installation - Mechanical
CLCH-SVX009J-EN
23
•
To lift unit with forklift, extend the forks under both
ends of the unit as indicated in the below figure. The
forks should extend past the end of the unit and should
not contact the bottom of the air handler. Units should
only be lifted from the proper end identified by the
lifting label on the unit.
Note:
Do not use a forklift on outdoor air handlers.
•
Lifting Indoor Units with Optional Baserail
For unit sizes 3 to 30, a forklift may be used to lift a single
section or small subassembly, provided the forks extend
under both ends of the base frame, or as indicated in the
figure below. The forks should not contact the bottom of
the air handler. Units should only be lifted from the proper
end identified by the lifting label on the unit. A lifting crane
or other means should be used for larger units where forks
cannot extend under both base rails.
Lifting Outdoor Units
Note:
For outdoor air handlers, preparation of the roof
curb or pier mount and roof openings must be
completed before lifting to the roof. See CLCH-
SVN-006*-EN Performance Climate Changer Air
Handler Model UCCA Roof Curb Installation.
•
When hoisting the unit into position, use the proper
rigging method, such as straps, slings, spreader bars
and lifting lugs for protection and safety.
•
Use
all
lifting lugs provided. See the figure below for
lug hole sizes and location.
Use field-provided spreader bars and slings to rig units
and subassemblies. The air handler is not designed to be
lifted or rigged from the top of the unit.
Figure 14.
Lifting detail for unit sizes 3 to 30
Figure 15.
Fork lift points
Figure 16.
Fork lift points with optional baserail
Rigging and spreader
bars furnished
by others
Side View
Figure 17.
Outdoor lifting lugs
2.50
Pipe cabinet
lifting lug
Hood lifting lug
1.25
2.50
Unit lifting lug
1.38