TEF 9980 STATUS LIGHT -
INSTALLATION AND USER MANUAL
7 FAILURE MODES
The TEF9980 constantly monitors the condition of the light by meas-
uring temperature, voltage and current. Failure is reported to control
system as described below. See also section “Lamp connections”.
Failures are grouped in two main modes; “alarm” and “warning”.
Warnings are considered to be corrected when environmental condi-
tions change. Alarms are considered to be permanent.
When light is OK, failure signal is “high”. If a failure occurs, failure signal
will go “low” and approx. every 5 seconds send out a pulse sequence
to indicate type of failure. Pulse width is 10ms and duty cycle is 0.5.
No. of pulses
Failure description
Action
0
Alarm: No power supply.
Lamp off.
1
Alarm: Internal comm. error, top LED circuit.
Lamp will not start up.
2
Alarm: Internal comm. error, middle LED circuit.
Lamp will not start up.
3
Alarm: Internal comm. error, bottom LED circuit.
Lamp will not start up.
4
Alarm: Top LED’s not blinking.
Lamp attempts continue working.
5
Alarm: Middle LED’s not blinking.
Lamp attempts continue working.
6
Alarm: Bottom LED’s not blinking.
Lamp attempts continue working.
7
Alarm: >10% of LED’s top not working.
Lamp attempts continue working.
8
Alarm: >10% of LED’s middle not working.
Lamp attempts continue working.
9
Alarm: >10% of LED’s bottom not working.
Lamp attempts continue working.
10
Alarm: Light intensity, top, out of bounds.
Lamp attempts continue working.
11
Alarm: Light intensity, middle, out of bounds.
Lamp attempts continue working.
12
Alarm: Light intensity, bottom, out of bounds.
Lamp attempts continue working.
13
Alarm: Light intensity, top, out of bounds or no light.
Lamp attempts continue working.
14
Alarm: Light intensity, middle, out of bounds or no light.
Lamp attempts continue working.
15
Alarm: Light intensity, bottom, out of bounds or no light.
Lamp attempts continue working.
16
Warning: Over-temperature LED’s top, level 1.
Half flash frequency. Resets automatically when
temperature drops below threshold.
17
Warning: Over-temperature LED’s middle, level 1.
Half flash frequency. Resets automatically when
temperature drops below threshold.
18
Warning: Over-temperature LED’s bottom, level 1.
Half flash frequency. Resets automatically when
temperature drops below threshold.
19
Warning: Over-temperature driver, level 1.
Half flash frequency. Resets automatically when
temperature drops below threshold.
20
Warning: Over-temperature LED’s top, level 2.
Goes to “dim mode”. Resets to level 1 when
temperature drops below threshold.
21
Warning: Over-temperature LED’s middle, level 2.
Goes to “dim mode”. Resets to level 1 when
temperature drops below threshold.
22
Warning: Over-temperature LED’s bottom, level 2.
Goes to “dim mode”. Resets to level 1 when
temperature drops below threshold.
23
Warning: Over-temperature driver, level 2.
Goes to “dim mode”. Resets to level 1 when
temperature drops below threshold.
24
Alarm: Over-temperature LED’s top, level 3.
Lamp off. Resets to level 2 when temperature
drops below threshold.
25
Alarm: Over-temperature LED’s middle, level 3.
Lamp off. Resets to level 2 when temperature
drops below threshold.
26
Alarm: Over-temperature LED’s bottom, level 3.
Lamp off. Resets to level 2 when temperature
drops below threshold.
27
Alarm: Over-temperature driver, level 3.
Lamp off. Resets to level 2 when temperature
drops below threshold.