Cable dimensions
Voltage drop in cables should be calculated to ensure that voltage at
lamp is minimum 16V. Use a current consumption of 6.15A for main
lamp and 0.41A for repeater light to calculate voltage drop.
Note:
• The control cabinet incorporates a regulated power supply, and
voltage out from cabinet can be considered to be 24VDC.
• Voltage drop in power supply cable will be compensated in
regulator.
• If necessary the voltage at control cabinet can be adjusted up to
28.5V.
One Main Light, Power Lines Wire 1 and 2 (Voltage at control cabinet = 24V)
Cable Length
Dimension
<60 meter
2,5mm
2
<100 meter
4mm
2
<140 meter
6mm
2
<230 meter
10mm
2
Repeater light and signal lines: Recommendation: Min. 1.5mm2 regardless of cable length (<300m).
Recommendation