Spare lamp test
Test of individual spare lamp:
1
Turn the respective circuit off.
2
Press and hold the respective button for min. 5 seconds.
3
Release button and spare lamp turns on.
Test of all spare lamps simultaneously:
1
Panel in standby mode.
2
Press and hold “on/standby” button for min. 5 seconds and while still “on/standby” is
pressed, press “backlight level” button. (Tip: While “on/standby” is pressed, press
“backlight level” repeatedly till spare lamp test mode starts.)
3
All spare lamp outputs are switched on.
4
Press “on/standby” to stop test.
Indicator lights, buttons:
Rapid green flashing: Circuit on, unconfirmed status.
Green steady: Main lamp on.
Slow green flashing: Spare lamp on.
Red flashing: Unacknowledged alarm.
Red Steady: Acknowledged alarm.
Alarm
Silence
On / Stby
Emcy. Supply Out
Main Supply Out
Level
Backlight
Spare Lamp Test