background image

 
 

http://www.tracopower.com 

 

Page 4 of 7 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 

 
 
 
2.3.1 Terminal assignment of connectors

 

 

3. Function 

3.1 Signalling 

 
The DC-IN-OK, BATT-OK and DC-OUT-OK outputs are for enabling monitoring of the functions of the TSP-BCMxx(A)), input 
and battery. The floating DC-IN-OK signal contacts (see Fig. 2.1 

 Connector J5, pin 1 & pin 2) are opened if the input voltage 

is not present. 
The floating BATT-OK signal contacts (see Fig. 2.1 

 Connector J5, pin 3 & pin 4) is monitoring if the battery can supply 

enough current for a given time.  
The floating DC-OUT-OK (see Fig. 2.1 

 Connector J5, pin 5 & pin 6) is available to monitor if the TSP-BCM12, TSP-BCM24(A) or 

TSP-BCM48(A) provides an output voltage. If the output voltage on the TSP-BCM24 or TSP-BCM24A is present, the relay contact 

 

(30Vdc / 0.6A or 60Vdc / 0.3A) is closed. It is detected by measuring the TSP-BCM12, TSP-BCM24(A) or TSP-BCM48(A) output 
voltage. 

TSP-BCM12, TSP-BCM24(A) & TSP-BCM48(A)

 

Pin No. 

J1 

J2 

J3 

J4 

J5 

J6  

Pin 1 

-Vin (DC In) 

GND (-) 

S+ 

15 sec test 

DC-IN-OK Signal 

Pos 2 

(factory setting)

  

(other settings see chapter 3.5)

 

Pin 2 

+Vin (DC In) 

GND (-) 

S- 

Com 

DC-IN-OK Relay contact 

 

Pin 3 

-Bat in 

Vout (+) 

10 min test 

BATT-OK Signal 

 

Pin 4 

+Bat in 

Vout (+) 

BATT-OK Relay contact 

 

Pin 5 

DC-OUT-OK Signal 

 

Pin 6 

DC-OUT-OK Relay contact 

 

Pin 7 

Remote ON/OFF 

 

Pin 8 

Remote ON/OFF 

 

Pin 9 

Temperature Sensing 

 

Pin 10 

Temperature Sensing 

 

Fig. 2.1:  Connectors of TSP Battery Module 