TRACO POWER TSP 070-112 Operating Instructions Manual Download Page 2

 
 

http://www.tracopower.com 

 

Page 2 of 7 

 

Disclaimer: 

Before installing and using the TSP-BCM 12, 

TSP-BCM24, TSP-BCM24A, TSP-BCM48 or TSP-BCM48A unit read the 

safety instruction provided with the unit.

 

1. Mechanical Mounting 

The TSP-BCM12 as well as the TSP-BCM24, TSP-BCM24A, TSP-BCM48 and TSP-BCM48A are “

Built in Devices

”, and 

must be mounted into an electrical rack which must provide protection against access to dangerous voltages, hot devices 
and be resistant to flammability and causing fire hazards.  The enclosure and mounting of the power supply must be 
compliant with the relevant national rules and regulations applicable for the mounting of automation appliances and devices 
or other relevant application regulations. 
The TSP-BCMxx(A) are designed for mounting on a DIN rail TS35 (DIN EN 50022-35x15/7.5) or for rack wall or chassis 
mounting using the wall mounting devices supplied on request.  
To fix device on the DIN-rail, hook top part of clip on DIN-rail, push down and inward until you hear a clipping sound. 
To remove the device, pull the latch of the clip with the aid of an insulated flat head screwdriver.  When clip has cleared 
bottom DIN rail remove the screwdriver from recess. Lift the device off DIN-rail. 
For mounting without DIN rails, a wall mounting bracket TSP-WMK01 (1 bracket, see ANNEX) can be supplied on 
request. With these brackets the TSP modules can be mounted directly to the wall. 
For wall mounting or chassis mounting remove the DIN-clips by removing the screw and place the mounting brackets in 
the same place as the DIN-clips. Use the countersink screws, which are included with the wall mounting kit (1 countersink 
screw with TSP-WMK01) to fix the mounting brackets on the TSP-BCMxx(A). Use a tightening torque of 0.8-0.9Nm. 
For all of the above mounting the correct position for optimal cooling performance must be observed. Above and below 
the TSP-BCMxx(A) a minimum free space of 80mm [3.15in] is required and on each side of the TSP-BCMxx(A) a 
minimum space of 25mm [1.0in] is required which allows air convection. The air temperature measured 10mm [0.39in] 
below the device must not exceed the specified values according the data sheet. Observe same power de-rating above 
ambient temperatures of 40°C as specified for the TSP power supplies. 

 
 

2. Electrical Connections 

2.1 Wire and Cable Requirements 

 

To achieve a reliable and shockproof connection strip the connecting ends according with table 2.1.1. If flexible wires are 
used the wires have to be terminated. (e.g. by using ferrules). 

All output terminals should be connected to the load. 
 

2.1.1 Connections wire table 

Input Device 

Terminals 

Function 

Solid or stranded wires 

Torque 

Stripping length 

[mm

2

[AWG] 

[Nm] 

[mm] 

TSP 090-124 
TSP 090-148 
TSP 180-124 
TSP 090-148 

+Vin & -Vin 

Input Voltage 

0.5 … 2.5 

24 … 12 

0.5 – 0.6 

7.0 

+Bat & -Bat 

Battery Voltage 

0.5 … 2.5 

24 … 12 

0.5 – 0.6 

7.0 

+Vout & -Vout  Output Voltage 

0.5 … 2.5 

24 … 12 

0.5 – 0.6 

7.0 

TSP 360-124 
TSP 360-148 

+Vin & -Vin 

Input Voltage 

1.0 … 2.5 

18 … 12 

0.5 – 0.6 

7.0 

+Bat & -Bat 

Battery Voltage 

1.0 … 2.5 

18 … 12 

0.5 – 0.6 

7.0 

+Vout & -Vout  Output Voltage 

1.0 … 2.5 

18 … 12 

0.5 – 0.6 

7.0 

TSP 600-124 
TSP 600-148 

+Vin & -Vin 

Input Voltage 

2.0 … 10.0 

12 … 7 

0.6 – 0.8 

7.0 

+Bat & -Bat 

Battery Voltage 

2.0 … 10.0 

12 … 7 

0.6 – 0.8 

7.0 

+Vout & -Vout  Output Voltage 

2.0 … 10.0 

12 … 7 

0.6 – 0.8 

7.0 

2.2 Step by Step Wiring Instructions 

Only qualified personnel should carry out the installation. The device is equipped with COMBICON connectors. This 
reliable and easy-to-assemble connection method enables a fast connection to the device. 
Following correct mounting of both the TSP Power Supply and the Battery Connector Module (BCM), the following steps 
should be followed to ensure correct connection and commissioning of the system. (Refer to Fig. 1.1, Fig 2.1; J2 and J3) 

 

1.  Make sure the mains power is switched off, secured against switch on and not yet connected to the power supply!  
2.  Next connect the TSP Power Supply output to J1 of the BCM (DC-IN). 