Table 6 Technical Information 

(*) Typical 

 

Note 1: Fully isolated power supply topology allows maximum 
flexibility in power supply configuration and eliminates ground loop 
issues. 

Input Voltage 

24-58v DC  

Input protection 

Reverse polarity protected 

Input/output  Isolation 

1000v [note 1] 

Outputs 

Output Voltage 

12v ±1v* 

Output Current [per channel/max normal 
operation] 

130ma* 

Output protection  

Fully short circuit protected, with auto re-start. 

Current window Alarm Threshold [max] 

170ma [+20%/-0%] 

Current window Alarm Threshold [min] 

50ma [+0%/-20%] 

Alarm Interface 

Volt free relay contacts [normally open and 
normally closed] 

Alarm Indication 

LED per sector and system status 

Environment 

Indoor / IP20 
-40 to +65

°C 

Dimensions mm  

See interface drawing 

Reliability [MTBF] 

>1000000 Hours 

Summary of Contents for radio design RD300 PDU

Page 1: ...tered In Scotland No 328828 Shipley Wharf Wharf Street Shipley West Yorkshire UK Tel 44 0 8452 770125 Fax 44 0 8452 770126 Email mail radiodesign eu Web www radiodesign eu Company Proprietary and Conf...

Page 2: ...echanical Installation 19 Rack Mounting The unit is primarily designed for 19 rack fitment using the included mounting screw set Un Mounted If no suitable mounting is available it is permissible to mo...

Page 3: ...de to the PDU in the following order 1 Earth connection 2 Connect Bias T 1 to 6 3 Connect alarm interface 4 Connect power Earth connection The front panel of the PDU has a 6mm Earth stud provided to e...

Page 4: ...2 of the interface cable PDU connector is not removed as this will result in the channel not being enabled Check The Connections to the BIAS T are not reversed Ensure that unused channel connections...

Page 5: ...PDU OFF Open circuit Short Circuit PDU ON Alarm Open circuit Short Circuit PDU ON No Alarms Short Circuit Open circuit N O normally open contact N C normally closed contact N O N C COM RAI 3 2 1 RD30...

Page 6: ...respect to PIN 2 Table 2 Power Connections shows the required connections for a positive or negative supply option The PDU is protected against reverse polarity connections but if the polarity is not...

Page 7: ...a TRAC company 99 438 Issue 05 Page 7 of 16 Connection Detail...

Page 8: ...be in a fault condition if the current drawn from the channel is outside the normal operational current i e the current draw is too high or too low When a channel first enters a fault state the contro...

Page 9: ...power cycle RED BLINK GREEN Output channel in alarm or NO channels enabled and unit has been through power cycle YELLOW This mode can only be reached by user intervention and indicates that the RESET...

Page 10: ...RED Channel is in fault condition Check each channel for fault indication Channel Indicator OFF but Bias T connected Link on connector between PINS 1 and 2 missing Fit link between pins 1 and 2 Chann...

Page 11: ...ut Isolation 1000v note 1 Outputs 6 Output Voltage 12v 1v Output Current per channel max normal operation 130ma Output protection Fully short circuit protected with auto re start Current window Alarm...

Page 12: ...a TRAC company 99 438 Issue 05 Page 12 of 16 Interface Drawings...

Page 13: ...a TRAC company 99 438 Issue 05 Page 13 of 16 Front Panel View...

Page 14: ...a TRAC company 99 438 Issue 05 Page 14 of 16 This page is intentionally blank...

Page 15: ...a TRAC company 99 438 Issue 05 Page 15 of 16 This page is intentionally blank...

Page 16: ...a TRAC company 99 438 Issue 05 Page 16 of 16 This page is intentionally blank...

Reviews: