![TR-Electronic CDH582 User Manual Download Page 56](http://html1.mh-extra.com/html/tr-electronic/cdh582/cdh582_user-manual_1146691056.webp)
Parameter description
TR-Electronic GmbH 2020, All Rights Reserved
Printed in the Federal Republic of Germany
Page 56 of 91
TR-ECE-BA-GB-0163 v03
10/07/2020
BYTE, BOOL
Value
Description
Default
0
Measuring system – position ascending clockwise
(looking at shaft, flange connection)
X
1
Measuring system – position descending clockwise
(looking at shaft, flange connection)
Link path,
Packed EPATH
with 8-bit class
0x20
0x23
0x24
0x01
0x30
0x0C
Logical Type =
Class
Class #23
Logical Type =
Instance
Instance #1
Logical Type =
Attribute ID Attribute ID #12
9.1.5 Preset Value
The Attribute
Preset Value
contains the adjustment value, which is set as the new position value if
the adjustment function is triggered via the Attribute
TR Grey – Preset Control
. The attribute is
integrated into the cyclic data traffic via the IO Assembly
Grey Output Channel 1 (adjustment function)
DINT, Default: 0
Byte
0
1
2
3
Bit
7-0
15-8
23-16
31-24
Data
2
7
– 2
0
2
15
– 2
8
2
23
– 2
16
2
31
– 2
24
9.1.6 TR Grey – Preset Control
The Attribute
TR Grey – Preset Control
(control word) contains the control bit for the
adjustment function and is integrated into the cyclic data traffic via the IO Assembly
Grey Output Channel 1 (adjustment function)
WORD
Byte
0
1
Bit
7-0
15-8
Data
2
7
– 2
0
2
15
– 2
8