TPI 6300/T Series Operating Instructions Manual Download Page 8

Model 

Heat 

Output 

Kw 

Norm. CFM 

Output 

Fan Speed 

RPM 

BTUH 

(1,000’s) 

Volts/HZ 

50/60 

Amps 

Copper Wire  

Size 75

°

AWG 

Maximum 

Fuse Size 

HI 

LO 

HI 

LO 

HI 

LO 

1PH 

3PH 

6333D052033B300F 

250 

230 

1550 

1400 

171/10.2 

208/60 

25.04

Π

 

17.57 

8/10 

35/25 

6333D052433B300F 

250 

230 

1550 

1400 

17.1/10.2 

240/60 

21.83

Π

 

15.38 

10/12 

30/20 

6333D054834B300F 

250 

230 

1550 

1400 

17.1/10.2 

277-480/60 

18.95

ΠΠ

 

8.02 

10/14 

25/15 

6333D054833B300F 

250 

1550 

17.1/10.2 

480/60 

7.76 

14 

15 

6333D055733B300F 

250 

1550 

17.1/10.2 

600/60 

5.48 

14 

15 

6346D102033B300F 

10 

500 

460 

1550 

1400 

34.1/20.5 

208/60 

49.98

ΠΠ

 

35.06 

6/8 

70/45 

6346D102433B300F 

10 

500 

460 

1550 

1400 

34.1/20.5 

240/60 

43.57

Π

 

30.68 

6/8 

60/40 

6346D104834B300F 

10 

500 

460 

1550 

1400 

34.1/20.5 

277-480/60 

37.70

ΠΠ

 

15.87 

6/12 

50/20 

6346D104833B300F 

10 

500 

1550 

34.1/20.5 

480/60 

15.35 

12 

20 

6346D105733B300F 

10 

500 

1550 

34.1/20.5 

600/60 

12.28 

12 

20 

 

STANDARD CABINET UNIT HEATER SPECIFICATIONS 

ISSUE DATE 06/15/01          REV. DATE  

REV. NO. 00           ECO NO. 1-4635       P/N 00009979                  SHT.08 OF 09 

Π

Comes factory wired as a 3-phase unit, can be field converted to single phase  

ΠΠ

comes factory wired as 480V/3-phase/4-wire unit, can be field converted to 277V/single phase 

 

 

  T 

46 

08 

24 

B3 

  A 

 B 

 D 

 E 

 H 

 I 

 K 

 

A) 

Series designation –T 

B) 

Cabinet size – 33 = 33 in., 46 = 46 in., 66 = 66 in., or 79 = 79 in. 

C) 

Inlet-outlet arrangement – A , B, C, or D 

D) 

Rating in KW – 02 through 24 

E) 

Voltage rating – 20 = 208V, 24 = 240V, 27 = 277V, 48 = 480V, or 57 = 600V 

F) 

Phase – 1 = 1phase or 3 = 3phase 

G) 

Number of wires in electric service – 2 = 2wires, 3 = 3wires, or 4 = 4wires 

H) 

Control option – B1 through B8, or ST 

I) 

Summer Fan Switch Option – S = Switch included or 0 = No switch 

J) 

Over current Protection Option – C = Circuit breaker included or 0 = No protection 

K) 

Motor Fusing Option – M = Motoring fuse included or 0 = No protection 

L) 

Filter Option – F = Filter included or 0 = No filter 

M) 

Disconnect Switch Option – D = Switch included or 0 = No switch 

N)  

Special Paint Color Option – P = Special color or Blank = Standard

 

Standard Unit Heaters are 33” and 46” wide. 

“CUSTOM-BUILT” CABINET UNIT HEATER 

MODEL NUMBER BREAKDOWN 

 

Summary of Contents for 6300/T Series

Page 1: ...bs 4 thru 12KW Heater W66 H25 D9 1 2 215lbs 6 thru 18KW Heater W79 H25 D9 1 2 248lbs 8 thru 24KW Heater SPECIFICATIONS Read all instructions before using this heater 1 Follow all local and electrical codes the National Electric code NEC and the Occupational Safety and Health Act OSHA 2 Before attempting any electrical connections or inspections for any reason to service the heater make sure that t...

Page 2: ... and 600 volt 3 phase units are all single speed only If external load management control of the unit is desired replace factory installed jumper wire on the control terminal block with leads from the external management control Refer to page 7 for description of control options OPERATING INSTRUCTIONS SYMPTOM POSSIBLE CAUSE S CORRECTIVE ACTION Heater does not energize 1 Defective thermostat 2 Defe...

Page 3: ...es are indicated for each mounting configuration In all positions clearance from end of heater to a side wall is zero inches Mounting holes are provided in the back of the cabinet accessible through the blower compartment If necessary remove blower deck if additional mounting screws or bolts are desired Blower deck may be slipped forward by loosening four screws at the front to provide access to m...

Page 4: ...s are provided in the back of the wiring compartment Make sure all field wiring connections are properly made and are tight Electrical Ground This heater must be grounded before operating as required by the National Electric Code and by applicable local codes Use a conductor of the appropriate size secured to the ground lug in the heater and to a grounded connection in the service panel Typical Wi...

Page 5: ...1 58027001 60719037 51135006 58027002 41017001 277 1 480 3 4 wire 1 2 3 51135006 58027002 N R 51135001 58027001 N R 51135001 58027001 60719011 51135006 58027002 41017009 480 1 480 3 3 wire 1 2 3 51135006 58027002 N R 51135001 58027001 N R 51135001 58027001 60719012 51135006 58027002 41017001 600 3 1 1 2 3 51135006 58027002 N R 51135001 58027001 N R 51135001 58027001 60719040 51135006 58027002 5834...

Page 6: ...001 Blower wheel 1 46 208 240 3 1 1 52290001 208 240V Motor Double shaft 1 415 3 4wire 52290001 208 240V Motor Double shaft 277 1 52290003 277V Motor Double shaft 480 3 3wire 1 52290004 480V Motor Double shaft 480 3 4wire 52290003 277V Motor Double shaft 600 3 1 52290005 575V Motor Double shaft All 3 1 2 62441001 Blower wheel 2 66 208 240 3 1 1 52289001 208 240V Motor single shaft 1 415 3 4wire 52...

Page 7: ...re operated by and internal 24 volt source B4 Built in single stage thermostat and relays which are operated by an internal 120 volt source also includes fusing in the fan circuit and the transformer primary B5 Built in two stage thermostat and relays which are operated by and internal 24 volt source B6 Built in two stage thermostat and relays which are operated by an internal 120 volt source also...

Page 8: ...NS ISSUE DATE 06 15 01 REV DATE REV NO 00 ECO NO 1 4635 P N 00009979 SHT 08 OF 09 ΠComes factory wired as a 3 phase unit can be field converted to single phase ΠΠcomes factory wired as 480V 3 phase 4 wire unit can be field converted to 277V single phase T 46 D 08 24 1 2 B3 S C M F D P A B C D E F G H I J K L M N A Series designation T B Cabinet size 33 33 in 46 46 in 66 66 in or 79 79 in C Inlet o...

Page 9: ...1 73 14 12 25 12 9 39 14 10 5 10 6 49 98 6 43 57 6 37 70 6 21 79 10 17 45 10 35 06 8 30 68 8 16 66 10 15 35 12 15 87 12 12 28 12 12 6 12 6 59 59 4 51 90 6 44 92 6 25 95 8 20 78 10 35 06 8 30 68 8 18 56 10 15 35 12 15 87 12 12 28 12 66 6 2 2 6 3 1550 1400 31 75 8 27 90 8 24 12 8 13 95 12 11 29 14 27 58 8 24 29 8 12 25 12 14 32 12 9 82 14 9 Π3 3 9 6 46 17 6 40 40 8 34 99 8 20 20 10 16 29 12 27 58 8 ...

Page 10: ...ion trim fr trim fr trim fr trim fr trim frames are for decor ames are for decor ames are for decor ames are for decor ames are for decora a a a a tive use onl tive use onl tive use onl tive use onl tive use only they are y they are y they are y they are y they are not not not not not made for supporting the cabinet unit hea made for supporting the cabinet unit hea made for supporting the cabinet ...

Page 11: ...ns or limitations may not apply to you During the warranty period TPI Corporation will at its sole option repair or replace any defective parts or products returned freight prepaid to the TPI Corporation factory or such other locations as TPI Corporation may designate Returned products must be packaged carefully and TPI Corporation shall not be responsible for damage in transit When returning part...

Reviews: