OPERATION DETAILS
DRY MODE OPERATION
•
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 360 seconds and the room temperature becomes 1.3
°
C lower than it was set.
•
The compressor will re-start when room temperature becomes 0.7
°
C higher than it was set.
•
The operational frequency will be set every 120 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.
Indoor fan
Selected speed
Stop
Super low
Super
low
3min.
0
Hz
Frequency of
compressor
Designated
temperature
Room temperature
Selected speed
-1.3˚C
0.7˚C
MAX
92Hz
MAX
92Hz
MIN 20Hz
MIN 20Hz