Labelling
Equipment shall be labelled stating that it has been de-commissioned and
emptied of refrigerant. The label shall be dated and signed. For appliances
containing
fl
ammable refrigerants, ensure that there are labels on the
equipment stating the equipment contains
fl
ammable refrigerant.
Recovery
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number
of cylinders for holding the total system charge are available. All cylinders
to be used are designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall
be complete with pressure-relief valve and associated shut-off valves in good
working order. Empty recovery cylinders are evacuated and, if possible, cooled
before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the
recovery of all appropriate refrigerants including, when applicable,
fl
ammable
refrigerants. In addition, a set of calibrated weighing scales shall be available
and in good working order. Hoses shall be complete with leak-free disconnect
couplings and in good condition. Before using the recovery machine, check
that it is in satisfactory working order, has been properly maintained and that
any associated electrical components are sealed to prevent ignition in the
event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant waste transfer note arranged. Do
not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they
have been evacuated to an acceptable level to make certain that
fl
ammable
refrigerant does not remain within the lubricant. The evacuation process shall
be carried out prior to returning the compressor to the suppliers. Only electric
heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.