94
GB
DEHUMIDIFIER / AIR PURIFIER
• No ignition sources
No person carrying out work in relation to a refrigeration system which involves
exposing any pipe work shall use any sources of ignition in such a manner
that it may lead to the risk of
fi
re or explosion. All possible ignition sources,
including cigarette smoking, should be kept suf
fi
ciently far away from the site
of installation, repairing, removing and disposal, during which refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the
area around the equipment is to be surveyed to make sure that there are no
fl
ammable hazards or ignition risks. «No Smoking» signs shall be displayed.
• Ventilated
area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and preferably expel it
externally into the atmosphere.
• Checks to the refrigeration equipment
Where electrical components are being changed, they shall be
fi
t for the
purpose and to the correct speci
fi
cation. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt, consult the
manufacturer’s technical department for assistance.
–
The actual refrigerant charge is in accordance with the room size within
which the refrigerant containing parts are installed.
–
The ventilation machinery and outlets are operating adequately and are not
obstructed.
–
If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant.
–
Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected.
–
Refrigeration pipe or components are installed in a position where they
are unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
• Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety