Installation
Installation
4.1.3. Precautions
ķ
The diameter of drainpipe should meet the drainage requirement at least.
ĸ
The drainpipe should be heat-insulated to prevent atomization.
Ĺ
Drainpipe should be installed before installing indoor unit. After powering on, there is some water in
water-receiver plate. Please check if the drain pump can operate correctly.
ĺ
All connection should be firm.
Ļ
Wipe color on PVC pipe to note connection.
ļ
Climbing, horizontal and bending conditions are prohibited.
Ľ
7KHGLPHQVLRQRIGUDLQSLSHFDQ¶WOHVVWKDQWKHFR
nnecting dimension of indoor drainpipe.
ľ
Heat-insulation should be done well to prevent condensation.
Ŀ
,QGRRUXQLWVZLWKGLIIHUHQWGUDLQDJHW\SHFDQ¶WVKDUHRQHFRQYHUJHQWGUDLQSLSH
4.2 Drainpipe Trap
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap.
4.2.2. Every indoor unit needs one drainpipe trap.
4.2.3. A plug should be designed to do cleaning.
P
l
u
g
50cm
50cm
4.3 Upwards drainage(drain pump)
4.3.1. To ensure the gradient 1/100, the drainpipe can be lifted to 340mm. After upwards, place downwards,
or it will cause malfunction to drain pump.
Summary of Contents for DCT 100HSPi
Page 1: ...Service Manual MODEL DCT 100HSPi o DCT 140HSPi o DCT 170HSPi o ...
Page 6: ...Indoor units Indoor units Part 2 Indoor units High Static Pressure Type ...
Page 9: ...Dimensions Indoor units 2 Dimensions 2 2 DCT 100HSPi 2 3 DCT 140HSPi DCT 170HSPi ...
Page 12: ...Wiring diagrams Indoor units 5 4 DCT 100HSPi 2 3 DCT 140HSPi DCT 170HSPi ...
Page 16: ...Static pressure Indoor units 10 Static pressure DCT 100HSPi DCT 140HSPi DCT 170HSPi ...
Page 19: ...Dimensions Outdoor units 1 3 DCT 100HSPo 1 4 DCT 140HSPo DCT 170HSPo ...
Page 21: ...Wiring diagrams Outdoor units 3 4 DCT 100HSPi 3 5 DCT 140HSPi DCT 170HSPi ...
Page 33: ...Installation Installation Part 4 Installation QVWDOODWLRQ ...
Page 41: ...Control Control Part 5 Control RQWURO ...
Page 45: ...Control Control ...