Electric characteristics
Outdoor units
5. Electric Characteristics
Model
Units
Compressor
OFM
Hz
Voltage
Min.
Max.
MSC
RLA
KW
FLA
DCT 100HSPo
50
380
342
418
61
6.58
250
1.38
DCT 140HSPo
50
380
342
418
66
8.22
65
0.7
DCT 170HSPo
50
380
342
418
67
9.77
65
0.7
Symbols:
MSC: Max. Starting Current
RLA: Rated Locked Current
OFM: Outdoor Fan Motor
FLA: Full Load Amps.
KW: Rate Motor Output
Notes:
1. RLA is based on the following conditions:
Indoor temp. 27
ć
DB/19
ć
WB
Outdoor temp. 35
ć
DB
2. MSC means the Max. current during the starting of compressor;
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
listed range limits;
4. Maximum allowable voltage variation between phase is 2%;
Summary of Contents for DCT 100HSPi
Page 1: ...Service Manual MODEL DCT 100HSPi o DCT 140HSPi o DCT 170HSPi o ...
Page 6: ...Indoor units Indoor units Part 2 Indoor units High Static Pressure Type ...
Page 9: ...Dimensions Indoor units 2 Dimensions 2 2 DCT 100HSPi 2 3 DCT 140HSPi DCT 170HSPi ...
Page 12: ...Wiring diagrams Indoor units 5 4 DCT 100HSPi 2 3 DCT 140HSPi DCT 170HSPi ...
Page 16: ...Static pressure Indoor units 10 Static pressure DCT 100HSPi DCT 140HSPi DCT 170HSPi ...
Page 19: ...Dimensions Outdoor units 1 3 DCT 100HSPo 1 4 DCT 140HSPo DCT 170HSPo ...
Page 21: ...Wiring diagrams Outdoor units 3 4 DCT 100HSPi 3 5 DCT 140HSPi DCT 170HSPi ...
Page 33: ...Installation Installation Part 4 Installation QVWDOODWLRQ ...
Page 41: ...Control Control Part 5 Control RQWURO ...
Page 45: ...Control Control ...