SUPPLY
PRESSURE
MANIFOLD
PRESSURE
CAUTION:
The gas line should be installed by a qualifi ed service person in accordance with all building
codes. This section is intended as a guide for qualifi ed technicians installing this appliance. Consult local and
/ or national building codes before proceeding.
Gas supply line access holes are located at the top and left sides of the Control Box. Gas valve inlet accepts
a 3/8" N.P.T. fi tting. Correct gas line diameter must be used to assure proper operation and pressure.
NOTE:
A sediment trap, as per national fuel gas code, must be installed in the gas supply line no more than 6
feet from the gas control valve to minimize the possibility of any loose scale or dirt within the gas supply line
from entering the control valve.
DO NOT HARD PIPE GAS LINE TO VALVE.
A method of disconnecting the valve from the gas line such as a
union or fl are fi tting must be provided to allow for repair or replacement of the gas valve.
Check local codes for additional requirements.
1. Connect the gas supply to the valve (Figure 27).
2. Turn on the gas supply and check that all connections are tight and leak free.
Correct gas pressure requirement:
Natural
Gas
Propane
Min. Pressure
5.0" WC
12.5" WC
(For purpose of input adjustment)
Max. Pressure
13.9" WC
13.9" WC
Manifold Pressure
Maximum
3.5" WC
10" WC
Minimum
1.6" WC
6.4" WC
Note:
To test the gas pressure, turn off the gas supply before removing the plug from the supply pressure
test port or manifold pressure test port.
Verify gas pressures with the fi replace lit and on the highest setting.
Please refer to the Burner Installation Manual for gas pressure
testing procedure.
Gas Supply / Connections
Gas Pressure Check
WARNING: The access panel including gasket must be reinstalled after conversion/installation or
servicing has been completed. Failure to do so will cause overheating and premature failure of the
control system.
Figure 34: Test ports.
5056.42523D2
19
TCWS38Dver2_140817-44