TOTALINE TOTALINE P707 Installation And Operation Instructions Manual Download Page 7

7

PITOT TUBE BALANCING PROCEDURE — The follow-
ing is a method of field balancing an HRV using a Pitot tube.
This is advantageous in situations when flow stations are not
installed in the ductwork. The procedure should be performed
with the HRV on high speed. See Fig. 24.

1. Operate all mechanical systems on high speed which

have an influence on the ventilation system (i.e., HRV,
forced air furnace, or air handler) if applicable. This
will provide the maximum pressure that the HRV will
need to overcome, and allow for a more accurate bal-
ance of the unit.

2. Drill a small hole in the return duct (about

3

/

16

-in.), 3 ft

downstream of any elbows or bends, and 1 ft upstream
of any elbows or bends. These are recommended
distances but the actual installation may limit the
amount of straight duct.

3. The Pitot tube should be connected to a Magnehelic

gage or other manometer capable of reading from 0 to
0.25 in. wg, preferably to 3 digits of resolution. The
tube coming out of the top of the pitot is connected to
the high pressure side of the gage. The tube coming
out of the side of the pitot is connected to the low pres-
sure or reference side of the gage.

4. Insert the pitot tube into the duct; pointing the tip into

the airflow. For general balancing it is sufficient to
move the pitot tube around in the duct and take an
average or typical reading.

5. Repeat this procedure in the supply duct. Determine

which duct has the highest airflow (highest reading on
the gage).

6. Use the HRV dampers to correct the airflow to match

the lower reading from the other duct. The flows
should now be balanced.

7. Actual airflow can be determined from the gage

reading. The value read on the gage is called the veloc-
ity pressure. The pitot tube comes with a chart that will
give the airflow velocity based on the velocity pressure
indicated by the gage. This velocity will be in either
feet per minute or meters per second. To determine
the actual airflow, the velocity is multiplied by the
cross-sectional areas of the duct being measured.

FORCED AIR

FURNACE

COOL AIR

RETURN

RETURN AIR

1 M

(3'-3") MIN

RECOMMENDED

* UNIT IS NORMALLY BALANCED ON HIGH SPEED 

WITH FURNACE BLOWER ON.

OUTDOORS

* DUCTS CONNECTION MAY VARY

DEPENDING ON MODEL

40" MIN

NOTES:

1. Furnace blower may be required to operate when ventilation from HRV is required. The furnace should be set to run continuously or inter-

locked with HRV.

2. A minimum separation of 39 inches (1 m) is required between the two direct connections.
3. The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.
4. Weather hood arrangement is for drawing purposes only. 6

 (2 m) minimum separation recommended. 18

 (460 mm) above grade minimum.

5. Due to the differences in pressure between the HRV and the equipment it is being connected to, the HRV’s airflow must be confirmed on site,

using the balancing procedure found in the installation manual.

Fig. 18 — Direct Connection to Furnace (Return/Return) Airflow Diagram

Fig. 19 — Direct Connection to Furnace

(Supply/Return)

Summary of Contents for TOTALINE P707

Page 1: ...ompo nents and equipment location roofs elevated structures etc Only trained qualified installers and service mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes GENERAL The P707 SHR1504 and P707 SHR2004 Heat Recovery Ventilators HRV are use...

Page 2: ...e There should be access to a water drain for condensate removal of the unit during defrost The unit should be located in a heated area attic installation is not recommended The location should also minimize any noise level that would be created by the unit in the living area Make sure there is adequate access for future maintenance Step 2 Unit Mounting The unit is typically hung from the ceiling ...

Page 3: ...ld be slightly larger than the collar to allow for the thickness of the insulated flexible duct See Fig 8 2 Cut a holes using the outline from Step 1 See Fig 8 When cutting or drilling holes be careful not to dam age electrical wiring or other hidden objects in wall 3 Pull the insulated flexible duct through the opening until it is well extended and straight Slide the duct inner vinyl sleeve over ...

Page 4: ...rically low voltage with the HRV accessory control contacts for intermittent demand To hard duct the supply air directly into the cold air return of the furnace remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10 Make sure that the minimum distance from the supply air of the HRV to the furnace is followe...

Page 5: ...n Stale air is drawn from key areas of home bathroom kitchen laundry Fresh air is supplied to main living areas The HRV must be balanced See Fig 14 Partially Dedicated System Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas via the forced air system HRV must be bal anced See Fig 15 and 16 SUPPLY EXHAUST BEDROOMS FRESH AIR EXHAUST AIR 1800 MM 4...

Page 6: ...re AIRFLOW STATION METHOD To measure airflow with an airflow station perform the following 1 Cut the duct and insert the flow measuring station Make sure that the flow measuring station air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape See Fig 21 2 Before taking the reading make sure that the Magne helic gage is level and at 0 See Fig 22 3 ...

Page 7: ...s the highest airflow highest reading on the gage 6 Use the HRV dampers to correct the airflow to match the lower reading from the other duct The flows should now be balanced 7 Actual airflow can be determined from the gage reading The value read on the gage is called the veloc ity pressure The pitot tube comes with a chart that will give the airflow velocity based on the velocity pressure indicat...

Page 8: ...d installation in the fresh air to building duct Install the damper and adjust as necessary DUCT DIAMETER in AREA sq ft 5 0 14 6 0 20 7 0 27 8 0 35 FORCED AIR FURNACE COOL AIR RETURN RETURN AIR 1 M 3 3 MIN RECOMMENDED UNIT IS NORMALLY BALANCED ON HIGH SPEED WITH FURNACE BLOWER ON OUTDOORS DUCTS CONNECTION MAY VARY DEPENDING ON MODEL 1 M 3 3 MIN RECOMMENDED NOTES 1 Furnace blower may be required to...

Page 9: ...stem For these thermostats use the alternate control contacts wiring See Fig 27 Magnehelic Magnehelic OUTDOORS PLACE PITOT TUBE A MINIMUM OF 18 FROM BLOWER OR ELBOWS NOTE DUCT CONNECTIONS MAY VARY DEPENDING ON MODEL MAGNEHELIC GAGE PITOT TUBE PITOT TUBE MAGNEHELIC GAGE Pitot tube should be kept at least 12 in away from fans elbows and dampers to ensure accurate reading Fig 24 Pitot Tube Balancing ...

Page 10: ...ering set the dehumidistat at its highest level and the switch on the HRV to standby If the Intellitek series controller is installed the air exchanger can be stopped at any time by turning the HRV off from the wall control However continuous ventilation is recommended Fall Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on...

Page 11: ...ated for life They require no maintenance Chassis The inside of the unit should be vacuumed yearly Be careful not to damage any of the mechanical compo nents and electrical connections Condensation Panel The condensation panel should be cleaned yearly Drain and Drain Line Units with drain lines should have their line and connection checked regularly Outside Hoods The outside hoods need to be check...

Page 12: ... clean core House grilles closed or blocked Check and open grilles Dampers are closed if installed Check and open dampers Poor power supply at site Have electrician check supply voltage at house Ductwork is restricting HRV operation Check duct installation Improper speed control setting Increase the speed of the HRV HRV airflow improperly balanced Have contractor balance HRV Supply Air Feels Cold ...

Page 13: ...BLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or inter...

Page 14: ......

Page 15: ......

Page 16: ...inue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P707 5SI CARRIER CORPORATION 2004 4 04 REPLACES New PRINTED IN U S A CATALOG NUMBER 570 332 ...

Reviews: