TOTALINE TOTALINE P707 Installation And Operation Instructions Manual Download Page 4

4

Step 6 — Install Indoor Ductwork System —

To

maximize airflow in the ductwork system, all ducts should be
kept short and have as few bends or elbows as possible. Forty-
five degree elbows are preferred to 90 degree elbows. Use tees
instead of 90 degree elbows whenever possible.

All duct joints must be fastened with screws or duct sealant

and wrapped with a quality duct tape to prevent leakage.
Aluminum foil duct tape is recommended. Galvanized ducting
from the HRV to the living areas in the house is recommended
whenever possible, although flexible duct can be used in
moderation when necessary.
SUPPLY AIR DUCTING — In homes without a forced air
furnace, fresh air should be supplied to all high-usage rooms
including bedrooms and living areas. Air should be supplied
from high wall or ceiling locations. Grilles that diffuse the air
comfortably are recommended. To avoid possible noise transfer
through the ductwork system, a short length (approximately
12 in.) of nonmetallic flexible insulated duct should be connect-
ed between the HRV and the supply/exhaust ductwork system.

The main supply and return lines to and from the HRV must

be 6 in. minimum. Branch lines to the individual rooms may
be as small as 4 in., but 5 in. lines are preferred. If floor
installation is the only option available, then special care
should be taken in locating grilles. Installation areas, such as
under baseboard heaters, will help to temper the air. In homes
with a forced air furnace, it may be advisable to connect the
HRV to the furnace ductwork (direct connection).

Building Codes and Combustion Appliance Installation

Codes do not allow location of return air grilles or any opening
such as a breathing tee in an enclosed room with spillage
susceptible combustion appliances.

The fresh air inlet from the HRV must be a minimum

distance of 3 ft from the furnace return drop to ensure proper
air mixing and temperature at the furnace core.

Direct Connection — A direct connection requires that the
furnace fan run continuously. See Fig. 13. The fan may be
inter-linked electrically (low voltage) with the HRV accessory
control contacts for intermittent demand.

To hard duct the supply air directly into the cold air return of

the furnace, remember to check the airflow balance of the HRV
with the furnace fan both on and off to determine that it does
not imbalance the HRV more than 10%. Make sure that the
minimum distance from the supply air of the HRV to the
furnace is followed. Refer to the local and National Building
and Heating Codes for any variations in these notes.
EXHAUST AIR DUCTING — The stale air exhaust system
is used to draw air from the points in the house where the worst
air quality problems occur. It is recommended that return air
ducts be installed in the bathroom, kitchen, and laundry room.
Additional return air ducts from strategic locations (i.e., green-
house, atrium, swimming pool, sauna, etc.) may be installed.
The furnace return duct may be also used.

In this method, the exhaust air is not ducted back from

bathrooms, kitchens, etc. to the HRV with dedicated lines.

This method has become popular and provides good

ventilation when installed in accordance with the instructions.
The furnace blower must be running when the HRV is operat-
ing for this method to be effective.
INSTALL DUCTING — To install indoor ductwork, perform
the following:

1. Begin with the duct collar on the HRV marked Exhaust

Air In. Slide a short piece (12-in.) of flexible duct over
the duct collar. Using duct tape, tape the flexible duct
to the collar.

2. Run the flexible ducting to the main rigid duct trunk

line, which connects to the remainder of the ducts
going to and from rooms in the house. Repeat the steps
for the Supply Air Out on the side of the HRV.

3. Working from a closet, attic or inside joist wall, run the

length of ducting required for the proper grille location
and cut a hole in the wall.

4. Fasten the mounting collar (field-supplied) to the duct-

ing and fasten the collar to the wall or ceiling with
screws.

5. The field supplied grille may be adjustable. It is rec-

ommended that the grilles be completely opened at
first and then adjusted later as needed.

6. Push the grille into the mounting collar or directly into

installed elbow.

Fig. 11 — Seal Hoods

Fig. 12 — Outdoor Ducting Installation

FROM HRV

Fig. 13 — Direct Duct Connection

Summary of Contents for TOTALINE P707

Page 1: ...ompo nents and equipment location roofs elevated structures etc Only trained qualified installers and service mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes GENERAL The P707 SHR1504 and P707 SHR2004 Heat Recovery Ventilators HRV are use...

Page 2: ...e There should be access to a water drain for condensate removal of the unit during defrost The unit should be located in a heated area attic installation is not recommended The location should also minimize any noise level that would be created by the unit in the living area Make sure there is adequate access for future maintenance Step 2 Unit Mounting The unit is typically hung from the ceiling ...

Page 3: ...ld be slightly larger than the collar to allow for the thickness of the insulated flexible duct See Fig 8 2 Cut a holes using the outline from Step 1 See Fig 8 When cutting or drilling holes be careful not to dam age electrical wiring or other hidden objects in wall 3 Pull the insulated flexible duct through the opening until it is well extended and straight Slide the duct inner vinyl sleeve over ...

Page 4: ...rically low voltage with the HRV accessory control contacts for intermittent demand To hard duct the supply air directly into the cold air return of the furnace remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10 Make sure that the minimum distance from the supply air of the HRV to the furnace is followe...

Page 5: ...n Stale air is drawn from key areas of home bathroom kitchen laundry Fresh air is supplied to main living areas The HRV must be balanced See Fig 14 Partially Dedicated System Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas via the forced air system HRV must be bal anced See Fig 15 and 16 SUPPLY EXHAUST BEDROOMS FRESH AIR EXHAUST AIR 1800 MM 4...

Page 6: ...re AIRFLOW STATION METHOD To measure airflow with an airflow station perform the following 1 Cut the duct and insert the flow measuring station Make sure that the flow measuring station air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape See Fig 21 2 Before taking the reading make sure that the Magne helic gage is level and at 0 See Fig 22 3 ...

Page 7: ...s the highest airflow highest reading on the gage 6 Use the HRV dampers to correct the airflow to match the lower reading from the other duct The flows should now be balanced 7 Actual airflow can be determined from the gage reading The value read on the gage is called the veloc ity pressure The pitot tube comes with a chart that will give the airflow velocity based on the velocity pressure indicat...

Page 8: ...d installation in the fresh air to building duct Install the damper and adjust as necessary DUCT DIAMETER in AREA sq ft 5 0 14 6 0 20 7 0 27 8 0 35 FORCED AIR FURNACE COOL AIR RETURN RETURN AIR 1 M 3 3 MIN RECOMMENDED UNIT IS NORMALLY BALANCED ON HIGH SPEED WITH FURNACE BLOWER ON OUTDOORS DUCTS CONNECTION MAY VARY DEPENDING ON MODEL 1 M 3 3 MIN RECOMMENDED NOTES 1 Furnace blower may be required to...

Page 9: ...stem For these thermostats use the alternate control contacts wiring See Fig 27 Magnehelic Magnehelic OUTDOORS PLACE PITOT TUBE A MINIMUM OF 18 FROM BLOWER OR ELBOWS NOTE DUCT CONNECTIONS MAY VARY DEPENDING ON MODEL MAGNEHELIC GAGE PITOT TUBE PITOT TUBE MAGNEHELIC GAGE Pitot tube should be kept at least 12 in away from fans elbows and dampers to ensure accurate reading Fig 24 Pitot Tube Balancing ...

Page 10: ...ering set the dehumidistat at its highest level and the switch on the HRV to standby If the Intellitek series controller is installed the air exchanger can be stopped at any time by turning the HRV off from the wall control However continuous ventilation is recommended Fall Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on...

Page 11: ...ated for life They require no maintenance Chassis The inside of the unit should be vacuumed yearly Be careful not to damage any of the mechanical compo nents and electrical connections Condensation Panel The condensation panel should be cleaned yearly Drain and Drain Line Units with drain lines should have their line and connection checked regularly Outside Hoods The outside hoods need to be check...

Page 12: ... clean core House grilles closed or blocked Check and open grilles Dampers are closed if installed Check and open dampers Poor power supply at site Have electrician check supply voltage at house Ductwork is restricting HRV operation Check duct installation Improper speed control setting Increase the speed of the HRV HRV airflow improperly balanced Have contractor balance HRV Supply Air Feels Cold ...

Page 13: ...BLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or inter...

Page 14: ......

Page 15: ......

Page 16: ...inue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P707 5SI CARRIER CORPORATION 2004 4 04 REPLACES New PRINTED IN U S A CATALOG NUMBER 570 332 ...

Reviews: