Multi Variable Air Conditioners Ducted Type Indoor Unit
5
(1) Installation of the unit must be in accordance with National Electric Codes and local
regulations.
(2) Improper installation will affect unit’s performance, so do not install the unit by yourself.
Please contact local dealer to arrange professional technicians for the installation.
(3) Do not connect power until all installation work is finished.
3.3 Wiring Requirements
(1) Power Cord Size and Air Switch Capacity
(1) Use copper wire only as unit’s power cord. Operating temperature should be within it
value.
(2) If the power cord is more than 15m (49-1/4 ft.) long, please increase properly the sectional
area of power cord to avoid overload, which may cause accident.
(3) Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at
40°C(104°F) Cambient temperature when laying across plastic pipe. Air switch is D type and
used at 40°C(104°F). If actual installation condition varies, please lower the capacity
appropriately according to the specifications of power cord and air switch provided by
manufacturer.
(4) Install cut-off device near the unit. The minimum distance between each stage of cut-off
device should be 3mm(1/8 in.) (The same for both indoor unit and outdoor unit).
Model
Power Supply
Fuse
Capacity(A)
TM09HSFDI
TM12HSFDI
TM18HSFDI
TM21HSFDI
TM24HSFDI
208/230V-1ph-60Hz
5
5
5
5
5