WX9 ASD Installation and Operation Manual
125
Search Inertia
Program
Protection
Retry/Restart
After a momentary power loss or the momentary loss of the
ST
-to-
CC
connection, this parameter sets the time for the commanded torque to reach its
programmed setting during the automatic restart. This function is in effect so
long as the
Retry/Restart
feature is enabled at
Auto Restart Selection
)
.
Settings:
0 — 0.5 Second (fast)
1 — 1.0 Second (standard)
2 — 1.5 Seconds
3 — 2.0 Seconds
4 — 2.5 Seconds
5 — 3.0 Seconds
6 — 3.5 Seconds
7 — 4.0 Seconds
8 — 4.5 Seconds
9 — 5.0 Seconds (slow)
Direct Access Number — F315
Parameter Type —
Selection List
Factory Default —
1.0
Changeable During Run —
No
Units — Seconds
Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the effective 100% output torque level while operating in
the
Drooping Control
mode. This value is the upper torque limit of the motor
being driven by a given ASD while operating in the
Drooping Control
mode.
Drooping
Drooping
Control
, also called
Load Share
, is used to share the load among
two or more mechanically coupled motors. Unlike
Stall
, which reduces the
output frequency in order to limit the load once the load reaches a preset level,
Drooping
can increase or decrease the V/f setting of a motor to maintain a
balance between the output torque levels of mechanically coupled motors.
Because of variances in gearboxes, sheaves, belts, motors, and because the
speed of the motor is constrained by the mechanical system, one motor may
experience more load than its counterpart and may become overloaded.
Drooping
Control
allows the overloaded motor to slow down, thus shedding
load and encouraging a lightly-loaded motor to pick up the slack. The goal of
Drooping
Control
is to have the same torque ratios for mechanically coupled
motors.
Direct Access Number — F320
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Speed at 0% Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the motor speed when at the 0% output torque gain while
operating in the
Drooping
Control
mode. This function determines the lowest
speed that
Drooping
will be in effect for motors that share the same load.
Direct Access Number — F321
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 299.0
Units — Hz
Summary of Contents for WX9 ASD
Page 2: ......
Page 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv WX9 ASD Installation and Operation Manual ...
Page 225: ......