RX2 Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the
RX2
input
terminal when this
terminal is used as the control input while operating in the
Torque Control
mode.
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
The bias and gain of the RX terminal may be trimmed at
,
respectively.
RX2 Torque Control Setup
Perform the following setup to allow the system to receive Torque Control
input at the
RX2
terminal:
•
Program
Fundamental
Standard Mode Selection
Frequency
Mode
RX2
•
Program
Fundamental
Standard Mode Selection
Command
Mode Selection
Terminal Board
•
Provide a
Run
command (F and/or R).
•
Set
RX2 Input Point 1 Torque
(
).
•
Set
RX2 Reference Point 1
) — the input analog signal level
that corresponds to the speed setting at
RX2 Input Point 1 Torque
.
•
Set
RX2 Input Point 2 Torque
(
).
•
Set
RX2 Reference Point 2
) — the input analog signal level
that corresponds to the speed setting at
RX Input Point 2 Torque
.
•
Provide a
Run
command (
F
and/or
R
).
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX2
level.
Once set, as the
RX2
voltage changes, the ASD output speed and/or torque will
vary in accordance with the above settings.
This parameter sets
RX2
Input Point 1 Torque
and is the output torque value
that is associated with the setting of
This value is entered as -250 to +250% of the rated torque.
See the
Expansion IO Card Option 1
instruction manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F226
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -250.0
Maximum — +250.0
Units — %
Torque Settings
RX2 Input Point 2 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the
RX2
input
terminal when this
terminal is used as the control input while operating in the
Torque Control
mode.
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX2
input level and motor load.
This parameter sets
RX2
Input Point 2 Torque
and is the output torque value
that is associated with the setting of
RX2 Reference Point 2
(
.
This value is entered as -250 to +250% of the rated torque.
Direct Access Number — F227
Parameter Type —
Numerical
Factory Default — +
100.0
Changeable During Run —
Yes
Minimum — -250.0
Maximum — +250.0
Units — %