Unified Controller Vm Series Controller typeS Instruction Manual
51
4.1.2 Operation mode switch
Switch
position
Operation mode
HALT
If you switch the operation mode switch from RUN or
PRUN to HALT, the main operation mode turns to the
HALT mode. If you turn the operation mode switch to
HALT and turn on the power, the unit starts in the HALT
mode. A RUN command from nV-Tool is accepted only
when the operation mode switch is set to RUN/PRUN.
RUN
If you switch the operation mode switch from HALT to
RUN, the main operation mode turns to the RUN mode. If
you switch the mode from PRUN to RUN, the operation
mode does not change.
PRUN
This means protect-RUN. The relationship with the
operation mode is the same as the RUN position. If the
mode is PRUN, the entire program may not be written.
Figure.4.2.
Operation mode switch setting
4.1.3 Ethernet IP Address Setting Switches for nV-Tool
Name
Description
STN-H
Upper digits (0 to F) of hexadecimal
converted from the lower 3 digits of
nV-Tool Ethernet IP address.
172.16.64.**
192.168.0.**
STN-L
Lower digits (0 to F) of hexadecimal
converted from the lower 3 digits of
nV-Tool Ethernet IP address.
172.16.64.**
192.168.0.**
Figure.4.3.
Ethernet IP address setting switch for nV-Tool
Important
Set either
「
172.16.64.**
」
or
「
192.168.0.**
」
of nV-Tool Ethernet IP address by the dip switch
No.5 and No.6.
「
0
」
cannot be specify for
「
**
」
.
Summary of Contents for typeS
Page 1: ...Unified Controller Vm Series Controller typeS Instruction Manual 6F8C1645 ...
Page 66: ...Chapter 3 Connecting Devices 6FC8C1645 48 ...
Page 80: ...Chapter 5 Program download 6F8C1645 62 ...
Page 84: ...Chapter 6 Operation 6F8C1645 66 ...
Page 87: ...Unified Controller Vm Series Controller typeS Instruction Manual 69 ...
Page 113: ...Chapter 8 Maintenance and Inspection 6F8C1645 94 ...
Page 127: ...Appendix A Specification 6F8C1645 108 ...
Page 155: ...Appendix C Notes on Applying the I O Modules 6F8C1645 136 ...
Page 157: ...1645 1 1912 ...