– 3 –
LN INTERFACE
Installation Manual
2
Introduction
Applicable air conditioners
TCC-LINK compatible air conditioners
Applications/Functions/Features
Applications
The LN interface is used to control TCC-LINK compatible Toshiba air conditioners by the building control system
using LON (Local Operating Network).
Functions
The LN interface converts signals between TCC-LINK signals for air conditioners and L
ON
W
ORKS
®
signals.
Features
The LN interface enables various settings such as air conditioner operation stop, temperature, operation mode
switching by the building control system, as well as monitoring of operating status, room temperature, various
settings, etc.
One LN interface has a capacity to control indoor units of up to 64 units.
A free topology FT-X1 transceiver is used as the L
ON
W
ORKS
®
transceiver (also communicatable with FTT-10A).
Specifications
External View
Name
LN interface
Model
TCB-IFLN642TLE
Power supply
220 - 240 VAC, 50/60 Hz
Power consumption
5 W
Number of connectable indoor units
64 units
Operating temperature/humidity
0 to 40 °C, 10 to 90% RH
Storage temperature
-20 to +60 °C (no condensation)
Dimensions
66 (H)×246 (W)×193 (D) mm
Mass
1.35 kg
193
77
246
246
63.6
66
77
193.4
219
234
193
6-Ø5.5
mounting holes
3-EN