Toshiba
– 4 –
LN INTERFACE
Installation Manual
EN
3
Before Installation
Check the following package contents.
Use the following wiring materials to connect the signal lines and power lines. (Locally procured)
4
Installation
Installation Method and Orientation
There are five installation methods as
shown in the figure: surface mount and wall
mount.
Do not install the unit in any other
orientation.
Use the attached screws.
REQUIREMENT
Do not install the unit in any of the following places.
• Humid or wet place
• Dusty place
• Place exposed to direct sunlight or at a high temperature
• Place where there is a TV set or radio within one meter
• Place exposed to rain (outdoors, under eaves, etc.)
Installation Space and Maintenance Space
A side space for connecting through cable inlets and an upper space for maintenance
must be reserved before installation.
The other sides can be adjacent to surrounding objects.
No.
Item
Quantity
Remarks
1
LN interface
1
2
Installation Manual
1
3
Screw
4
M4 x 12mm tapping screws
4
Clamp filter
1
5
Tie-wrap
1
For fixing the clamp filter
No.
Line
Description
1
For TCC-LINK
Type
2-core shield wires
Wire size
1.25 mm
2
, 1000m max.
2.00 mm
2
, 2000m max.
(total length including air conditioner
area)
Length
2
For L
ON
W
ORKS
®
Type
Twisted pair shield cable (dedicated cable or equivalent)
Wire size
0.65 mm × 1P
Length
Free topology : 500 m max. (total length)
Bus topology : 1000 m max.
3
For power
Type
H07 RN-F or 245IEC66
0.75mm
2
, 50 m max.
Wire size
No good
Good
100mm
100mm
4-EN
+00DE93419101-1_00Ta.book Page 4 Wednesday, February 9, 2011 5:27 PM