T1000 Series UPS 1000-3000VA Installation and Operation Manual
– 94086-001
19
After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been
fully discharged. The UPS could be damaged if the unit is not fully discharged before the
breaker is reset.
MAINTENANCE NOTE
The T1000 Series UPS is not designed for field-level service. All repairs will be done at the
Depot-level.
12 INSTALLATION
12.1
ENVIRONMENT
Ensure that all environmental concerns and requirements are met according to these
technical specifications, otherwise the safety of installation personnel cannot be
guaranteed and the unit may malfunction.
Follow below instructions when locating the UPS system and battery options:
Avoid extreme temperature and humidity. Maximal battery life can be attained with a
recommended temperature range of 15 °C to 25 °C.
Protect the equipment from moisture.
Space and ventilation requirements must be met. Ensure there are 100mm behind
and 50mm on the sides of the UPS for ventilation.
Ensure that the front of the UPS remains clear for user operation.
The External Battery Cabinets has to be installed next to the UPS or under the UPS.