Strata CTX100 Installation
Environmental Considerations
provides a summary of the environmental characteristics.
AC Power and Earthing Requirements
The CTX100 requires an earth connection back to the main distribution point for proper operation and
safety. Failure to provide this earth may be a safety hazzard or lead to confusing fault, or operational
symptoms and,in extreme cases, system failure. The AC power cord already contains a conductor for
the “protective earth” provided by the commercial power outlet. This alone is not sufficient. It is also
necessary to connect a seperate insulated conductor between the Frame Ground (FG) terminal on the
base KSU and the main distribution point. (See
). This must be installed in accordance with
the general rules for earthing contained in BS6701 parts 1 & 2.
Note
Please note, no plug is fitted to the European version of CTX100 Product. Please refer to
the chapter ‘Notes to Users’ at the end of this manual, which defines the power
connection method
.
CAUTION!
Lack of proper ground may cause improper operation and, in extreme cases, system
failure.
Table 2-1
CTX100 Environmental Characteristics
Environmental Specifications
Operating temperature
Operating humidity
Storage temperature
32~104° F (0~40° C)
20~80% relative humidity without condensation
-4~140° F (-20~60° C)
BTU Rating (Base plus Expansion Cabinet)
ACTU (installed)
BDKU (5 installed)
RCOU/RCOS (1 installed)
Digital Telephones (40 installed)
190 Watts (56 watt hours for both cabinets)
Power
Supply
Third Wire
AC Ground
Expansion cabinets are NOT terminated
with plugs and must be hardwired to
a fused spur.
CTX 100 Base Cabinet
A
Electrical Building
Ground (Main Power
Distribution Box)
Alternate Ground
AC Voltage
220-240VAC
AC Current
1 amp max.
5911ctx
135cm (4' 5")
Fused Spur
Figure 2-2
CTX100 Grounding Diagram
Summary of Contents for Strara CTX Series
Page 10: ...Contents viii Strata CTX I M September 2002 ...
Page 14: ...Introduction xii Strata CTX I M September 2002 ...
Page 52: ...Strata CTX Configuration 1 38 Strata CTX I M September 2002 ...
Page 176: ...ISDN Interfaces 5 28 Strata CTX I M September 2002 ...
Page 278: ...Peripheral Installation 8 32 Strata CTX I M September 2002 ...