No.
Piping parts
Name
Selection of pipe size
Remarks
(7)
Branching
section
Branching
header
Selection of branching section (Branching header)
Total capacity code of indoor units
Model name
Equivalent to capacity (HP)
*2
Branching header
For 4 branches
Below 14.2
RBM-HY1043E
14.2 to below 25.2
RBM-HY2043E
For 8 branches
Below 14.2
RBM-HY1083E
14.2 to below 25.2
61.2 or more
RBM-HY2083E
*2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one
line after branching of header. When the total capacity codes of all outdoor units are 12
to below 26 (equivalent to HP) and you use a branching header for the ?rst branching
section, use a RBM-HY2043E or RBM-HY2083E regardless of the total capacity codes
of outdoor units at downstream side. In addition, you cannot use a branching header for
the ?rst branching section when the total capacity codes of all outdoor units are over 26
(equivalent to HP).
(8)
Branching
section
Outdoor unit
connection
piping kit
(For linking of
outdoor units)
Outdoor unit connection piping kit (For linking of outdoor units)
Total capacity code of
outdoor units
*3
Model name
Outdoor unit
connection piping kit
(For linking of outdoor
units)
Equivalent to capacity
(HP)
Below 26
RBM-BT14E
26 to below 62
RBM-BT24E
62 or more
RBM-BT34E
*3: Upstream side when regarding the main piping as the start point