6. Operation in Parameter Setup Mode
6-3
3
Using the control dial, select/confirm the
setting you want to change by selecting a
menu item or specifying a value.
(In this example, “Panel / LCD-option” is
selected and confirmed or a frequency of
90.0Hz is specified and confirmed.)
When the change you made is saved, the title of
the parameter stops blinking and the screen
returns to the previous window.
6.3 Use the guidance function (Only VF-MB1)
When use with a VF-MB1 inverter, you can use the Guidance function.
The Guidance function displays only necessary parameter for each function.
1
Select/confirm “Guidance function” using the
control dial in Basic Parameters window.
The Guidance function window appears.
Functions of function keys
: Brings you to the Top View Mode.
: Displays the previous window.
: Displays the next window.
Functions of function keys
: Displays the previous window.
: Displays the next window.
●
If the setting selected is
changed by specifying a
value
Basic Parameters
vL
×100
×1000
×10
×1
90.0
Hz
Base frequency 1
min=25.0
max=500.0
●
If the setting selected is
changed by selecting a
menu item
Basic Parameters
CMOd
Command input mode
0 :Terminal
1 :Panel / LCD-option
口
2 :RS485-2wire
3 :RS485-3wire
∨
F1
F2
F3
F1
F2
F3
F2
F3
Parameter Setup Mode
Basic Parameters
Top
AUF :
Guidance
function
AU1 :
Overload
characteristic
AU2 :
Automatic
acc/dec
AU4
: Automatic torque boost
CMOd : Command input mode
Basic Parameters
AUF
Guidance function
0: No function
口
1: No function
2: Preset speed
3: Analog signal operation
F2
F3