Confirmation of indoor unit No. position
1. To know the indoor unit addresses though position of the indoor unit body is recognized
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
1
Push
button if the unit stops.
2
Push
button.
Unit No.
1-1
is displayed on LCD.
(It disappears after several seconds.)
The displayed unit No. indicate line address and
indoor unit address.
(When other indoor units are connected to the
identical remote controller (Group control unit), other
unit numbers are also displayed every pushing
button.
UNIT
SET
CL
UNIT No.
CODE No.
1
1 2
2
END
Operation
<Operation procedure>
UNIT
SET
CL
UNIT No.
SET DATA
R.C.
No.
1
1 2 3
2
3
END
<Operation procedure>
2. To know the position of indoor unit body by address
• To confirm the unit No. in the group control
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are succes-
sively displayed, and fan, flap, and drain pump of the
corresponding indoor unit are turned on. (Follow to the
procedure during operation)
1
Push
and
buttons simultaneously for 4
seconds or more.
• Unit No.
ALL
is displayed.
• Fans and flaps of all the indoor units in the group
control operate.
2
Every pushing
button, the unit numbers in
the group control are successively displayed.
• The unit No. displayed at the first time indicates the
master unit address.
• Fan and flap of the selected indoor unit only
operate.
3
Push
button to finish the procedure. All the
indoor units in the group control stop.