10-8-7.
Central Control Address Number Setting
To connect an indoor unit to the central control remote controller, an address number for central control must
be set.
• An address number for central control is indicated as the refrigerant line number of the remote controller.
1 Setting by Remote Controller on Indoor Unit Side
<Procedure>
Perform the following steps in the operation OFF mode.
1
Push
TEST
and
VENT
on the remote controller simultaneously for 4 seconds or more.
When group control is going, UNIT No.
is displayed first, and all indoor units in the group are se-
lected. At this time, the fans of all the selected indoor units start running. (Fig. 1)
Maintain this state without pushing
UNIT LOUVER
.
For individual remote controllers without group control, a refrigerant line address and an indoor unit
address are indicated.
2
Specify code
!
with
TEMP.
buttons.
3
Choose setting data with
TIME
buttons.
Table 1 shows setting data.
4
Push
SET
Indication on the LCD shows normal operation.
• To change an item for setting, return to
2
.
5
Push
TEST
to return to the normal indication.
(Fig.1)
ON / OFF
SET
TEST
FILTER
RESET
CL
VE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
No.
MODE
AN
SET DATA
SETTING
4
2 5
1
3
Table 1
Setting data
0001
0002
0003
|
0064
0099
Address No. for
central control
1
2
3
|
64
Not set
(factory setting)
FILE NO. SVM-
12004
–
82
–