background image

– 9 –

Maintenance

WARNING

Cleaning the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have 
a qualified installer or qualified service person to do it.

 

Do not attempt it by yourself.

7

Cleaning air filters

Clogged air filters will reduce the cooling and heating performance.

1) If “ ” is displayed on the remote controller, clean the air filters.
2) When the cleaning of air filters has been completed, push 

 button.

 

“ ” disappears. 

When not used for a long time

1. Perform the fan operation for a couple of hours to dry inside.
2. Push 

 button on the remote controller to stop running, and turn off the circuit breaker.

3. Clean the air filters and reinstall them.

Before the cooling season

Clean the drain pan

• Contact the dealer where you purchased the product.

 

(Drain does not work if the drain pan or vent is clogged. In some cases the drain may overflow and wet the wall 
or floor. Clean the drain pan before the cooling season.)

Check periodically

• If the unit is used for a long time, parts may deteriorate and cause malfunction or bad drainage of dehumidified 

water depending on the heat, humidity, or dust.

• In addition to the usual maintenance, it is recommended that you have the unit checked and maintained by the 

dealer where you purchased it.

NOTE

For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in 
use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.

 

When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended. 

 

Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof treatment, if 
necessary.

 

As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit at 
least once every 3 months. Ask a professional for this cleaning / maintenance work.

 

Such maintenance can extend the life of the product though it involves the owner’s expense.

 

Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and even 
compressor failure.

(1)

(2)

Maintenance List

Part

Unit

Check (visual / auditory)

Maintenance

Heat exchanger

Indoor / outdoor

Dust / dirt clogging, scratches

Wash the heat exchanger when it is clogged.

Fan motor

Indoor / outdoor

Sound

Take appropriate measures when abnormal 

sound is generated.

Filter

Indoor

Dust / dirt, breakage

• Wash the filter with water when it is 

contaminated.

• Replace it when it is damaged.

Fan

Indoor

• Vibration, balance
• Dust / dirt, appearance

• Replace the fan when vibration or balance is 

terrible.

• Brush or wash the fan when it is contaminated.

Air intake / 

discharge grilles

Indoor / outdoor

Dust / dirt, scratches

Fix or replace them when they are deformed or 

damaged.

Drain pan

Indoor

Dust / dirt clogging, drain 

contamination

Clean the drain pan and check the downward 

slope for smooth drainage.

Ornamental panel, 

louvers

Indoor

Dust / dirt, scratches

Wash them when they are contaminated or apply 

repair coating.

Exterior

Outdoor

• Rust, peeling of insulator
• Peeling / lift of coat

Apply repair coating.

17-EN

18-EN

+00EH99939501_01EN.book  Page 9  Thursday, January 12, 2012  4:31 PM

Summary of Contents for RAV-SM1106BT-E

Page 1: ... Indoor Unit Model name Concealed Duct Type RAV SM406BTP E RAV SM456BTP E RAV SM566BTP E RAV SM806BTP E RAV SM1106BTP E RAV SM1406BTP E RAV SM1606BT E English For commercial use P 00EH99939501_01EN book Page 1 Thursday January 12 2012 4 31 PM ...

Page 2: ...rson who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has b...

Page 3: ...st this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks After the installation work has been completed have the installer explain about the circuit breaker positions In the event that trouble has occurred in the air conditioner set the circuit breaker to the OFF position and contact a service person If the...

Page 4: ...ing is completed Do not modify the products Do not also disassemble or modify the parts It may cause a fire electric shock or injury Relocation When the air conditioner is to be relocated do not relocate it yourself but contact a qualified installer 1 or a qualified service person 1 Failure to relocate the air conditioner properly may result in electric shocks and or a fire CAUTION To disconnect t...

Page 5: ...acking notice In case that cardboard boxes protrude out of pallet when stacking lay a 10 mm thick plywood over the pallet 5 cartons 2 Part names Indoor unit Outdoor unit The design varies depending on the outdoor unit The following illustration shows an example Air discharge Connect a discharge duct Electrical control box The earth screw is provided in the electrical control box Drain pan Air inta...

Page 6: ...TIMER SET TEST FILTER RESET TEMP CL FAN SAVE SWING FIX VENT MODE ON OFF UNIT LOUVER Display section Operation section 1 8 6 16 4 2 3 5 7 13 15 14 1 9 12 11 10 7 Auto High Med Low 11 UNIT No display The selected indoor unit number is displayed Also number of indoor or outdoor unit which an error occurs is displayed 12 Central control display Displayed when the air conditioner is used under the cent...

Page 7: ...also be sensed For details contact the dealer from which you have purchased the air conditioner 8 6 4 3 2 5 7 10 12 1 9 11 4 Correct usage When the air conditioner is used for the first time or when the setting is changed follow the steps below Settings are saved in memory and are displayed anytime the unit is turned on by pushing the button Preparation When the circuit breaker is turned on the pa...

Page 8: ...you ask service staff for periodic maintenance of the air conditioner 1 Set the displayed temperature to 18 C in the heating mode by pushing TEMP button 2 Set the displayed temperature to 8 C by pushing TEMP button for at least 4 seconds 1 Set the displayed temperature to 18 C by pushing TEMP button The air conditioner returns to the normal HEAT mode Select a desired temperature and operation mode...

Page 9: ...the setting of power level Each push of the button changes the power level by 1 within the range from 100 to 50 The factory default is 75 4 3 1 5 2 UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode 4 Push button 5 Push button to complete the setting NOTE When other electric appliances are used at the same time to avoid triggering the circuit breaker power ...

Page 10: ...he air conditioner is operated for a long time periodic maintenance once a year is recommended Furthermore regularly check the outdoor unit for rust and scratches and remove them or apply rustproof treatment if necessary As a general rule when an indoor unit is operated for 8 hours or more daily clean the indoor unit and outdoor unit at least once every 3 months Ask a professional for this cleanin...

Page 11: ... Discharged air smells unusual Various smells from the walls carpet clothes cigarette cosmetics or other things adhere to the air conditioner The unit does not run Has a blackout occurred Has the circuit breaker blown Has the protective device been activated The operation indicator and on the remote controller are blinking Check again The room does not cool down or warm up Is the air intake or dis...

Page 12: ...bove conditions safety protection may work Cooling operation Outdoor temperature 15 C to 43 C Dry bulb temp Room temperature 21 C to 32 C Dry bulb temp 15 C to 24 C Wet bulb temp CAUTION Room relative humidity less than 80 If the air conditioner operates in excess of this figure the surface of the air conditioner may cause dewing Heating operation Outdoor temperature 15 C to 15 C Wet bulb temp Roo...

Page 13: ...ow Generic Denomination Air Conditioner Model type RAV SM406BTP E RAV SM456BTP E RAV SM566BTP E RAV SM806BTP E RAV SM1106BTP E RAV SM1406BTP E RAV SM1606BTP E Commercial name Digital Inverter Series Super Digital Inverter Series Air Conditioner Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law Declaration of incorporation...

Page 14: ...ss city country Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom 144 9 Moo 5 Bangkadi Industrial Park Tivanon road Amphur Muang Pathumthani 12000 Thailand 00EH99939501_01EN book Page 109 Thursday January 12 2012 4 31 PM 1115460101 TOSHIBA CARRIER THAILAND CO LTD 144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...

Reviews: