– 19 –
4-way Air Discharge Cassette Type
Installation Manual
Wire connection
REQUIREMENT
• Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Be sure to pass the wires through the bushing of wiring connection port of the indoor unit.
• Keep a margin (Approx. 100mm) on a wire to hang down the electric parts box at servicing, etc.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
• Remove the cover of the electric parts box by taking off the mounting screws (2 positions) and pushing
the hooking section. (The cover of the electric parts box remains hanged to the hinge.)
• Connect the indoor/outdoor connection wires and remote controller wire to the terminal block of the
electric parts box.
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electric parts box.
(Do not apply tension to the connecting section of the terminal block.)
• Using the attached thermal insulation material, seal the pipe connecting port. Otherwise, dewing may
be caused.
• Mount the cover of the electric parts box without pinching wires.
(Mount the cover after wiring on the ceiling panel.)
1 2 3
A
B
Hinge
Screws a 2 positions
Louver connector
(CN510:White)
Side D (Space: 8.5mm)
Side C (Space: 4mm)
Select side C or D for the power cable clamping
position referring to the following table according to
the cable type and diameter.
* Cable clamp can be attached on either right or left
side.
When twin system are connected, clamp two cables
with one cable clamp.
Wire
type
Specification
Cable clamping
position
Cabtyre
cable
4-core stranded
wire 2.5mm²
Side D
Cabtyre
cable
4-core stranded
wire 1.5mm²
Side C
Adhered surface
Notched section
▼
Thermal insulation to wiring
connecting port
Power supply terminal block
Remote
controller
terminal
block
Cord clamp
19-EN