– 82 –
DN
Item
Description
At shipment
F6
Presence of Application
control kit
(TCB-PCUC2E)
0000: None
0001: Exist
0000: None
d0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid
0001: Valid
0001: Valid
b7
Occupancy sensor
operation at absent time
0000: Stand by
0001: operation stop
0000: Stand by
F0 Swing mode
0001 : Standard
0003 : Cycle swing
0002 : Dual swing
0001: Standard
F1
Louver fixed position
(Louver No.1)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F2
Louver fixed position
(Louver No.2)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F3
Louver fixed position
(Louver No.3)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F4
Louver fixed position
(Louver No.4)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
b3 Soft cooling
0000: Unavailable
0001: Available
0001: Available
C2 Power saving
0050: 50%
to
0100: 100%
0075: 75%
E0 Destination
0000: Japan
0004: Global
0004: Global
Fb Power shift
0000: Unavailable
0001: Available
0000: Unavailable
FC
Communication
protocol *2
0000: TCC-LINK
0004: TU2C-LINK
0004: TU2C-LINK
C7
Secondary heating c
Temp.(TO
H
-TO
L
)"
0000: Unavailable
0001: 1°C
to
0010: 10°C
0000: Unavailable
C6
Secondary heating
Set Temp. out (high)
-0015: -15°C
to
0015: 15°C
0000: 0°C
db
Secondary heating a
Temp.(TA
H
-TA
L
)
0001: 0.5°C
to
0010: 5.0°C
0006: 3.0°C
d1
8°C heating
Frost protective
operation
0000: Unavailable
0001: Available
0000: Unavailable
dc
Secondary heating a
Temp.
Normal mode (Ts-TA
H
)
Flip mode (TA
L
-Ts)
0000: Unavailable
0001: 1°C
to
0010: 10°C
0000: Unavailable
C5
Secondary heating
mode
0000: Normal mode
0001: Flip mode
0000: Normal mode
Occupancy sensor/
Wireless remote
controller
Provided / None
b5
0000: None
0002: Wireless remote controller
provided
0001: Occupancy sensor
provided
0000: None
b6
Occupancy sensor
Enable/Invalid
(Absence time judgment
time)
0000: Invalid
0002: 60min.
0005: 150min.
0001: 30min.
0004: 120min.
0002: Enable
(60 min.)
77 Dual set point
0000: Unavailable
0002: Available
0000: Unavailable
9A
Thermostat OFF fan
speed in cooling mode
0000: Remote controller setting
0002: Fan OFF
0001: Extremely low speed (UL)
0003: Low speed (L)
0001: Extremely low
speed (UL)
120 Defrost shift
0000: Unavailable
0001: Available
0001: Available
121 Draft prevention control 0000: Unavailable
0001: Available
0001: Available
1C1 Rotation operation
0000: Unavailable
0001: Available
0000: Unavailable
1C2 Rotation interval
0001: 1 day
to
0028: 28 days
0001: 1 day
1C3 Rotation lap time
0000: 0
to
0007: 70 minutes
0003: 30 minutes
1C9 Free Cooling ON Temp. -0015: -15°C
to
0029: 29°C
0016: 16°C
1CA Free Cooling OFF Temp. -0015: -15°C
to
0029: 29°C
0010: 10°C
1C8 Free Cooling
0000: Unavailable
0001: Available
0000: Unavailable
1Cb
Free Cooling ON/OFF
differential Temp."
0000: 0
to
0010: 10°C
0002: 2°C
*1 Display order of “00Un”and “0099” varies depending on remote controller models or communication types.