[F30 trouble]
Is connection
of the occupancy
sensor connector
(CN214) normal?
Correct the connector
connection.
Is DN code [B5] setup?
By the wired remote
controller, change the
enable DN code [B5] from
[0000]
→
[0001]
Replace the indoor
P.C. board (MCC-1643).
No
Yes
Is the Occupancy
sensor unit normal?
Exchange the Occupancy
sensor unit
No
Yes
No
Yes