– 14 –

Heat insulation process

Apply heat insulation for the pipes separately at liquid 
side and gas side.
• For the heat insulation to the pipes at gas side, use 

the material with heat-resisting temperature 120°C 
or higher.

• Apply the attached heat insulation to the pipe 

connecting section of the indoor unit securely without 
gap.

REQUIREMENT

• Apply the heat insulation to the pipe connecting 

section of the indoor unit securely up to the root 
without exposure of the pipe. (The pipe exposed to the 
outside causes water leak.)

• Wrap heat insulator with its slits facing up (ceiling 

side).

Indoor unit

Union

Heat insulation

pipe

(Accessory)

Flare nut

Heat insulator 

of the pipe

Wrap the pipe with the attached heat insulator 

without any gap between the indoor unit.

The seam must be faced upward 

(ceiling side).

Banding band 

(Accessory)

7

Electrical connection

WARNING

Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces applied 
to the terminals from affecting the terminals.

Incomplete connection or fixation may cause a fire or other trouble.

Connect earth wire. (grounding work)

Incomplete earthing cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.

Appliance shall be installed in accordance with national wiring regulations.

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.

Under no circumstances, the power supply wire or the indoor and outdoor connecting wire must not be 
connected in the middle (Connection using a solderless terminal etc.) 

Connection trouble in the places where the wire is connected in the middle may give rise to smoking and/or a fire.

CAUTION

CAUTION

• For power supply specifications, follow the Installation Manual of outdoor unit.
• Do not connect 220 – 240 V power to the terminal blocks (

) for control wiring.

Otherwise, the system will fail.

• Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during 

peeling them.

• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.

The coating may melt resulting in an accident.

• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.

Wiring specifications

Indoor / Outdoor connecting wires specifications

Indoor unit power supplied from outdoor unit

• The outdoor unit power supply patterns vary on models.

*Number of wire × wire size
*Including earth line

Remote controller wiring

* The remote controller wiring length differs depending on the remote controller used. For details, refer to the Installation 

Manual attached to the remote controller.

CAUTION

CAUTION

The remote controller wire and Indoor / Outdoor connecting wires cannot be parallel to contact each other and cannot 
be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other factor.

Indoor unit power supply 

1~50 Hz   220 - 240 V
1~60 Hz   220 V

Indoor / Outdoor connecting wires*

4 × 1.5 mm² or more (H07 RN-F or 60245 IEC 66)*

Up to 70 m

Remote controller wiring, remote controller inter-unit wiring

Wire size: 2 × 0.5 to 2.0 mm²

Total wire length of remote controller wiring and remote 

controller inter-unit wiring = L + L1 + L2 + … Ln

In case of wired type only

Up to 500 m

2 remote controllers

Up to 300 m

In case of wireless type included

Up to 400 m

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 200 m

A

B

27-EN

28-EN

Summary of Contents for RAV-HM1101UT-E

Page 1: ...AIR CONDITIONER SPLIT TYPE Installation Manual R32 Indoor Unit 4 way Cassette type RAV HM561UT E RAV HM801UT E RAV HM1101UT E RAV HM1401UT E Model name For commercial use English ...

Page 2: ...erant HFC R32 which does not destroy the ozone layer This indoor unit is for the R32 refrigerant Be sure to combine with an outdoor unit for the R32 refrigerant Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping ...

Page 3: ... pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge ...

Page 4: ...t in water leakage electric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit ...

Page 5: ...r conditioner is running Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Appliance and pipe work shall be installed operated and stored in a room with a floor area larger than Amin m How to get Amin m Amin M 2 5 0 22759 h0 M is the refrigerant charge amount in appliance in kg h0 is the installa...

Page 6: ...on using a solderless terminal etc Connection trouble in the places where the wire is connected in the middle may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and Installation Manual Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the w...

Page 7: ...ossibly resulting in rupture injury or other trouble 1 Refer to the Definition of qualified installer or qualified service person This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer As the R32 refrigerant is easily affected by impurities such as moisture oxidized film oil etc due to the high pressure be careful not to allow the moisture dirt existing refri...

Page 8: ...lly Place where a sufficient servicing space can be ensured for safety maintenance and check Place where drained water will not cause any problem Avoid installing in the following places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring The unit should be used in these places special protective measures are needed A restaurant k...

Page 9: ...sible to be installed Unit m REQUIREMENT When using the air conditioner with 2 way 3 way discharge system a strong wind blows directly if the ceiling height is lower than the standard Therefore change the setting switch according to height of the ceiling When high ceiling 1 or 3 is used with 4 way blowing a draft is easily recognized due to drop of discharge temperature The lighting time of the fi...

Page 10: ...AV A B C HM56 type 6 4 12 7 256 HM80 type 9 5 15 9 319 HM110 type 9 5 15 9 319 HM140 type 9 5 15 9 319 External view Unit mm 1 8 7 6 1 5 7 6 4 Z 45 840 Unit outer dimensions Ceiling bottom surface Ceiling bottom surface 840 Unit outer dimensions 780 Suspension bolt pitch 860 to 910 Ceiling opening size 950 Panel outer dimensions Refrigerant pipe connecting port Liquid A Electrical control box Refr...

Page 11: ...cs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Panel mounting screw Installation pattern Accessory Push in the panel mounting screw into this hole to set the installation pattern New concrete slab Install the bolts with insert brackets or anchor bolts...

Page 12: ...g unit enables two indoor units installed in a room to be respectively operated using two wireless remote controllers 7 m o r le s s 5 Drain piping CAUTION CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of fur...

Page 13: ...e band tightening allowance 5 mm or less 10 12 mm Heat insulating material Flexible hose Accessory Hard polyvinyl chloride pipe socket for VP25 Locally procured Hard polyvinyl chloride pipe VP25 Locally procured 10 mm Drain pipe connecting port Color transparent Rising up 661 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less After the electric work has finished po...

Page 14: ...2 7 mm 15 9 mm Liquid side 6 4 mm 9 5 mm Outside diameter size R32 or R410A tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outside diameter size A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 B A Tightening connection CAUTION CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Incorrect connection...

Page 15: ...re is connected in the middle may give rise to smoking and or a fire CAUTION CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during peeling them Perfo...

Page 16: ...connect able units 16 8 This letter indicates U series model This letter indicates U series model This letter indicates U series model L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller For number of Max connect able units refer to the following table Remote controller wiring Wiring between indoor unit and outdoor unit 1 Figure below sh...

Page 17: ...n of the terminal board 4 Seal the wiring connecting port with the attached heat insulation material Otherwise this may result in condensation 5 Attach the cover of the electrical control box without pinching the wires Mount the cover after wiring the ceiling panel Screw A Hinge Hook section Cover of the electrical control box Screw B Hinge Louver connector CN510 White MCU Cover of the electrical ...

Page 18: ... it with two screws without pinching the wires 7 Attach the cover of the electrical control box without pinching the wires Mount the cover after wiring the ceiling panel Wiring cover Hinge Cover of the electrical control box Screws Screws A Hook section Screws B Hinge Louver connector CN510 White MCU Cover of the electrical control box Seal material 1 2 3 A B Side D height 8 5 mm Side C height 4 m...

Page 19: ...the remote controller becomes available Normal settings were made when the indoor unit was shipped from factory Change the indoor unit settings as required Use the wired remote controller to change the settings The settings cannot be changed using the wireless remote controller sub remote controller or remote controller less system for central remote controller only Therefore install the wired rem...

Page 20: ... High ceiling 3 OFF ON SW501 2 SW501 1 MCU IC501 To secure better effect of heating When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator or other machinery to circulate heat air near the ceiling Follow to the basic operation procedure 1 2 3 4 5 6 7 Specify 0...

Page 21: ... for the set data in Procedure 5 Set data Wind direction setting 0000 Smudge reducing position Air direction to reduce ceiling contamination Factory default 0002 Cold draft less position Air direction to control cold air fall F1 F3 F4 04 01 03 02 F2 Indoor unit drain pipe Indoor unit refrigerant pipe Electrical control box 0000 Setting data Set data Remote controller sensor 0000 Not in use Factory...

Page 22: ...roup by a remote controller Outdoor unit Remote controller Indoor unit Indoor unit Finish of address setup by power ON Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Remote controller Outdoor unit Outdoor unit Outdoor unit Outdoor unit Finish of address setup by power ON Example Group control for complex system The above address is set by the automatic addressing when the...

Page 23: ...h the wired remote controller as usual For the procedure of the operation refer to the attached Owner s Manual A forced test run can be executed in the following procedure even if the operation stops by thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION CAUTION Do not use the forced test run ...

Page 24: ...perature to 17 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 30 C with the temp setup buttons Monitoring function This function can be used to call the service monitor mode from the remote controller during a test run to obtain the temperature of the sensors of the remote controller indoor unit and outdoor unit 1 Push and hold menu ...

Page 25: ... effectively by washing with water or lukewarm water dissolved a neutral detergent 4 Attach the air filter 5 Close the air intake grille Close the air intake grille slide the two hooks towards the outside and secure it properly Hook Air intake grille Hook Cleaning of discharge louver The discharge louver can be removed for cleaning 1 Remove the corner cap 2 Remove the discharge louver Hold both en...

Page 26: ...st dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ceiling panel louvers Indoor Dust dirt...

Page 27: ...or P C board Open circuit or short circuit of the room temp sensor TA was detected Auto reset F12 ALT TS sensor trouble Outdoor TS sensor may be displaced disconnected or short circuited Entire stop F13 ALT Heat sink sensor trouble Outdoor Abnormal temperature was detected by the temp sensor of the IGBT heat sink Entire stop F15 ALT Temp sensor connection trouble Outdoor Temp sensor TE TS may be c...

Page 28: ...leakage from the pipe or connecting part Check for gas leakage Entire stop P19 ALT 4 way valve trouble Outdoor Indoor 4 way valve indoor temp sensors TC TCJ An trouble was detected due to temperature drop of the indoor unit heat exchanger sensor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan trouble Outdoor O...

Page 29: ...EB99847501 DH91308101 ...

Reviews: