– 18 –
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Wiring on the ceiling panel
As per the Installation Manual of the ceiling panel, connect the connector (20P: White) of the ceiling panel to the
connector (CN510: White) onto the P.C. board within the electrical control box.
1
3
10
50
10
70
2
Indoor / Outdoor connecting wires
Earth wire
2 mm
o
r
le
ss
Indoor / Outdoor connecting wires
See the figure on the left for
system interconnection wires to
the terminal block.
A
B
A
B
Terminal block
Remote
controller
unit
Terminal block for
remote controller
wiring of indoor unit
Remote controller wire
(Locally procured)
8
Applicable controls
• For using the wired remote controller RBC-AMS55E ,
refer to the Owner’s Manual attached to the wired
remote controller.
REQUIREMENT
• When you use this air conditioner for the first time, it
takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote controller
becomes available.
<When power is turned on for the second (or later)
time>
It takes
approx. 1 minute
until the remote controller
becomes available.
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
* The settings cannot be changed using the
wireless remote controller, sub remote controller,
or remote-controller-less system (for central
remote controller only). Therefore, install the
wired remote controller to change the settings.
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU1
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
CAUTION
Set only the Code No. shown in the following table: Do
NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
1
Push and hold menu button and [
] setting
button simultaneously for 10 seconds or
more.
• After a while, the display flashes as shown in the
figure. “ALL” is displayed as indoor unit numbers
during initial communication immediately after the
power has been turned on.
Power on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 5 minutes
Power on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 1 minutes
3,6
4,5 1
7
2,4,5
Indoor unit No.
35-EN