- 91 -
EN-181
EN-182
Existing pipes: Cannot be used.
• Use new pipes.
Connect the indoor/outdoor units to the existing pipe.
• Use a flare nut attached to the main unit for the
indoor/outdoor units. (Do not use the flare nut of the
existing pipe.)
• Re-machine the flare machining size to size for R32.
• After the existing air conditioner is operated in cooling
mode for approx. 30 minutes or longer,* recover the
refrigerant.
• Refer to “13 Refrigerant recovery”
• For cleaning the pipes and recovering oil
• Refrigerant recovery: Pump down method
Was largely discolored oil or a large quantity
of remains discharged? (When the oil
deteriorates, the color of the oil changes to a
muddy or black color.)
Clean the pipes or use new pipes.
NO
YES
YES
YES
NO
NO
Are there scratches or dents on the existing pipes?
Is it possible to operate the existing air conditioner?
• (Airtight test), Vacuum dry, Refrigerant charge, Gas leak
check
Test run
[2] Minimum floor area: Amin (m
2
)
* Total refrigerant quantity: Refrigerant quantity pre-
charged at f Additional refrigerant quantity
charged during installation
Total
refrigerant
quantity*
Floor
standing
unit
Wall
mounted
unit
Ceiling
mounted
unit
h
0
0.6
1.8
2.2
M (kg)
A
min
(m
2
)
3HP
1.90
30.98
3.44
2.30
1.92
31.63
3.51
2.35
1.94
32.29
3.59
2.40
1.96
32.96
3.66
2.45
1.98
33.64
3.74
2.50
2.00
34.32
3.81
2.55
2.02
35.01
3.89
2.60
2.04
35.71
3.97
2.66
2.06
36.41
4.05
2.71
2.08
37.12
4.12
2.76
2.10
37.84
4.20
2.81
2.12
38.56
4.28
2.87
2.14
39.30
4.37
2.92
2.16
40.03
4.45
2.98
2.18
40.78
4.53
3.03
2.20
41.53
4.61
3.09
2.22
42.29
4.70
3.15
2.24
43.05
4.78
3.20
2.26
43.83
4.87
3.26
2.28
44.61
4.96
3.32
2.30
45.39
5.04
3.38
2.32
46.18
5.13
3.44
2.34
46.98
5.22
3.49
2.36
47.79
5.31
3.55
2.38
48.60
5.40
3.62
2.40
49.42
5.49
3.68
2.42
50.25
5.58
3.74
2.44
51.09
5.68
3.80
2.46
51.93
5.77
3.86
2.48
52.77
5.86
3.93
2.50
53.63
5.96
3.99
2.52
54.49
6.05
4.05
2.54
55.36
6.15
4.12
2.56
56.23
6.25
4.18
2.58
57.12
6.35
4.25
2.60
58.00
6.44
4.31
2.62
58.90
6.54
4.38
2.64
59.80
6.64
4.45
2.66
60.71
6.75
4.52
2.68
61.63
6.85
4.58
Max. 2.70
62.55
6.95
4.65
4HP
5HP
3.1
82.46
9.16
6.13
3.135
84.33
9.37
6.27
3.17
86.22
9.58
6.41
3.205
88.14
9.79
6.56
3.24
90.07
10.01
6.70
3.275
92.03
10.23
6.85
3.31
94.01
10.45
6.99
3.345
96.01
10.67
7.14
3.38
98.03
10.89
7.29
3.415
100.07
11.12
7.44
3.45
102.13
11.35
7.60
3.485
104.21
11.58
7.75
3.52
106.32
11.81
7.91
3.555
108.44
12.05
8.07
3.59
110.59
12.29
8.23
3.625
112.75
12.53
8.39
3.66
114.94
12.77
8.55
3.695
117.15
13.02
8.71
3.73
119.38
13.26
8.88
3.765
121.63
13.51
9.05
3.8
123.90
13.77
9.22
3.835
126.20
14.02
9.39
3.87
128.51
14.28
9.56
3.905
130.84
14.54
9.73
3.94
133.20
14.80
9.91
3.975
135.58
15.06
10.08
4.01
137.98
15.33
10.26
4.045
140.39
15.60
10.44
4.08
142.83
15.87
10.62
4.115
145.30
16.14
10.81
4.15
147.78
16.42
10.99
4.185
150.28
16.70
11.18
4.22
152.81
16.98
11.37
4.255
155.35
17.26
11.56
4.29
157.92
17.55
11.75
4.325
160.50
17.83
11.94
4.36
163.11
18.12
12.13
4.395
165.74
18.42
12.33
4.43
168.39
18.71
12.53
4.465
171.06
19.01
12.72
4.5
173.76
19.31
12.92
4.535
176.47
19.61
13.13
4.57
179.20
19.91
13.33
4.605
181.96
20.22
13.53
4.64
184.74
20.53
13.74
Max. 4.675
187.53
20.84
13.95
Total
refrigerant
quantity*
Floor
standing
unit
Wall
mounted
unit
Ceiling
mounted
unit
h
0
0.6
1.8
2.2
M (kg)
A
min
(m
2
)