- 80 -
CAUTION
• Do not put the crescent wrench on the cap or cover.
The valve may break.
• If applying excessive torque, the nut may break
according to some installation conditions.
• After the installation work, be sure to check for gas
leaks of the pipe connections with nitrogen.
• Therefore, using a torque wrench, tighten the flare
pipe connecting sections that connect the indoor/
outdoor units at the specified tightening torque.
Incomplete connections may cause not only a gas
leak, but also trouble with the refrigeration cycle.
Do not apply refrigerating machine oil to the flared
surface.
Cover
Piping valve
Tightened
Flare nut
Cap
Loosened
Valve at gas side
<GP110, GP140>
Cover
Cap
Incorrect
Refrigerant Pipe Length
Single
Outdoor unit
Allowable pipe length (m)
Height difference (m)
Total length
Indoor-outdoor H
Minimum
Maximum
Indoor unit: Upper
Outdoor unit: Upper
GP80
3
50
30
30
GP110, 140
3
75
30
30
Outdoor unit
Pipe diameter (mm)
Number of bent portions
Gas side
Liquid side
GP80
15.9
9.5
10 or less
GP110, 140
15.9
9.5
10 or less
H
Indoor unit
Figure of single
Outdoor unit
EN-159
EN-160