– 116 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[1C]
(Continued)
[Communication error between MCUs]
[Communication error between MCUs]
[1D]
[Compressor lock]
[1E]
[Discharge temp. error]
Are connections of CN802 on P.C.B MCC-5071
and CN802 on P.C.B MCC-1571 correct?
Correct connection.
Check outdoor P.C. Boards.
Defect • Replace.
YES
NO
Are connections of CN804 on P.C.B MCC-5071
and CN800 on P.C.B MCC-1571 correct?
Correct connection.
Check outdoor P.C. Boards.
Defect • Replace.
YES
NO
Is AC mains voltage correct?
(198 to 264V)
Check wiring construction.
Ask repair of power supply.
NO
Is wire connection correct?
Compressor lead
(Board side, Compressor Side),
Reactor lead, Power supply lead.
Check wire connection
and correct it.
YES
NO
Is compressor under correct condition?
Check outdoor P.C.B MCC-1571.
Defect • Replace.
Is there refrigerant stagnation?
Compressor lock • Replace.
NO
YES
NO
YES
Check outdoor P.C.B MCC-5071.
Defect • Replace.
Does PMV correctly operate?
Check TE, TS sensors and PMV.
Detect • Replace.
NO
YES
YES
Is PMV under correct conditions?
Is connection of CN600 on P.C.B. MCC-5071?
Is resistance value of TD sensor correct?
Is there gas leak?
Is there refrigerant shortage?
Repair defective position.
Recharge refrigerant.
Correct connector.
Sensor error • Replace.
Check outdoor P.C.B MCC-5071.
Defect • Replace.
Repair defective position.
Replace defective part.
Does an abnormal overload happen?
Remove and improve
the cause of overload.
YES
YES
NO
NO
NO
NO
YES
YES