3) Pushing SW02, the display changes to next item. To see other display contents, repeat that.
4) To finish LED display, be sure to execute item 1) to return LED to the initial status (error display of current
occurrence) and then finish LED display.
[Error display]
The error which is occurring at present and the latest error (including error that is occurring now) can be confirmed
by checking display on the outdoor control P.C. board.
A.Error display which occurs at present
○:ON (○*:3 sec ON/0.5 sec OFF)●:OFF
◎:Rapid Flashing(5 times/sec) ◇:Slow Flashing(1 time/sec)
Display
Indoor
Description
D800 D801 D802 D803 D804 D805 check code
(YL)
(YL)
(YL)
(YL)
(YL)
(GN)
●
●
●
●
●
-
Normal operation (no error)
○*
●
●
●
●
1C
Compressor case thermostat error
●
○*
●
●
●
21
High pressure switch error
○*
○*
●
●
●
1C
Compressor system error
●
●
○*
●
●
1D
Compressor lock
○*
●
○*
●
●
1F
Compressor breakdown
●
○*
○*
●
●
14
Driving element short circuit
○*
○*
○*
●
●
16
Position detection circuit error
●
●
●
○*
●
17
Current detection circuit error
○*
●
●
○*
●
1C
Communication error between MCU
●
○*
●
○*
●
1A
Fan system error
○*
○*
●
○*
●
1E
Discharge temperature error
●
●
○*
○*
●
19
Discharge temperature sensor (TD) error
*1 ○*
●
○*
○*
●
1B
Outdoor air temperature sensor (TO) error
●
○*
○*
○*
●
18
Suction temperature sensor (TS) error
○*
○*
○*
○*
●
18
Heat exchanger temperature sensor (TE) error
*2
●
●
●
●
○*
1C
Gas pipe (unit A) temperature sensor (TGa) error
*2 ○*
●
●
●
○*
1C
Gas pipe (unit B) temperature sensor (TGb) error
*2
●
○*
●
●
○*
1C
Gas pipe (unit C) temperature sensor (TGc) error
○*
●
○*
●
○*
-
PMV error (SH≥20)
●
○*
○*
●
○*
-
PMV error (SH≤–8)
●
●
●
○*
○*
20
PMV leakage error (unit A)
○*
●
●
○*
○*
20
PMV leakage error (unit B)
●
○*
●
○*
○*
20
PMV leakage error (unit C)
○*
●
○*
○*
○*
-
Miswiring (mispiping) check error
∗1: Back-up operation is performed without error display of the indoor unit.
∗2: Operated normally when the air conditioners in other rooms are driven.
B.Error display of the latest error (including error which occurs at present)
○:ON (*:3 sec ON/0.5 sec OFF)●:OFF
◎:Rapid Flashing(5 times/sec) ◇:Slow Flashing(1 time/sec)
Display
Indoor
Description
D800 D801 D802 D803 D804 D805 check code
(YL)
(YL)
(YL)
(YL)
(YL)
(GN)
●
●
●
●
●
-
Normal operation (no error)
◎
●
●
●
●
1C
Compressor case thermostat error
●
◎
●
●
●
21
High pressure switch error
◎
◎
●
●
●
1C
Compressor system error
●
●
◎
●
●
1D
Compressor lock
◎
●
◎
●
●
1F
Compressor breakdown
●
◎
◎
●
●
14
Driving element short circuit
◎
◎
◎
●
●
16
Position detection circuit error
●
●
●
◎
●
17
Current detection circuit error
◎
●
●
◎
●
1C
Communication error between MCU
●
◎
●
◎
●
1A
Fan system error
◎
◎
●
◎
●
1E
Discharge temperature error
●
●
◎
◎
●
19
Discharge temperature sensor (TD) error
◎
●
◎
◎
●
1B
Outdoor air temperature sensor (TO) error
●
◎
◎
◎
●
18
Suction temperature sensor (TS) error
◎
◎
◎
◎
●
18
Heat exchanger temperature sensor (TE) error
●
●
●
●
◎
1C
Gas pipe (unit A) temperature sensor (TGa) error
◎
●
●
●
◎
1C
Gas pipe (unit B) temperature sensor (TGb) error
●
◎
●
●
◎
1C
Gas pipe (unit C) temperature sensor (TGc) error
◎
●
◎
●
◎
-
PMV error (SH≥20)
●
◎
◎
●
◎
-
PMV error (SH≤–8)
●
●
●
◎
◎
20
PMV leakage error (unit A)
◎
●
●
◎
◎
20
PMV leakage error (unit B)
●
◎
●
◎
◎
20
PMV leakage error (unit C)
◎
●
◎
◎
◎
-
Miswiring (mispiping) check error
○
◇
FILE NO. SVM-18020
-2
- 69 -