[Confirmation method of various settings]
You can confirm that various settings are validated.
1) Check LED displays are in the initial status. If it are not so, return them to the initial status.
2) Push and hold SW01 for 5 seconds or more. D804 changes to slow flashing.
3) Push SW01 several times and then stop it at the point where LED display (D800 to D804) to be checked. If
the setting became valid, D804 and D805 flash rapidly. (When the setup was invalid, D804 flashes rapidly
and D805 goes off.)
4) Push SW01 and SW02 for 5 seconds or more simultaneously to return LED display to the initial status.
○:ON (○*:3 sec ON/0.5 sec OFF)●:OFF
Display
◎:Rapid Flashing(5 times/sec) ◇:Slow Flashing(1 time/sec)
No.
D800 D801 D802 D803
D804
D805
Item
Control contents
(YL) (YL) (YL) (YL)
(YL)
(GN)
Refrigerant collection operation
Miswiring (mispiping) check
Fan motor operation check
PMV operation check
Cooling only setting
Heating only setting
Power save function
Select current limit
*1. Item and setting is displaying.
*2. Item and setting is selecting.
8
○
○
●
○
7
●
○
●
○
6
●
●
●
○
5
○
○
○
●
4
●
○
○
●
●
○
●
○
3
2
●
●
○
●
1
○
●
●
●
When using the power save function, set the switch. The current limit is
enabled. When the setting is finished, the display is as below.
If you enabled the power save function, you have to choose two of the
current limit value. When the setting is finished, the display is as below.
(1)8.5A
(2)11.0A
◇
*1
or
◎
*2
●/○
*1
or
●/◎
*2
The outdoor unit performs cooling operation. As the indoor unit does not
operate by this switch setting only, carry out the operation beforehand.
(Before switch setting, you have to operate in cooling mode of all indoor
units.) During the check, the display is kept as below.
*Operation is up to 10 minutes.
*After the collection is finished, promptly stop the operation of all the indoor
unit. (There are cases that the compressor restarts.)
The outdoor unit performs cooling operation. As the indoor unit does not
operate by this switch setting only, carry out the operation beforehand.
(Before switch setting, you have to operate in cooling mode of all indoor
units.) During the check, the display is kept as below.
*Operation is up to 30 minutes.
*You cannot check wiring/piping when the external temperature is 5℃ or less.
*During the check, the compressor and the fun of the outdoor/indoor unit
repeat ON/OFF.
Operate the fan motor forcedly. The motor rotates at 500rpm and operation is
2 minutes. During the check, the display is kept as below.
PMV is initialized to order from unit A. (only one time)
Checking its operation sound and you can see that it is operating. During the
check, the display is kept as below.
When using the air conditioner as a cooling-only conditioner, set the switch.
(If the heating mode is selected by remote controll, outdoor unit will remain
stop. If mixed with indoor unit cooling and heating, outdoor unit performs
cooling operation.) When the setting is finished, the display is as below.
When using the air conditioner as a heating-only conditioner, set the switch.
(If the cooling mode is selected by remote controll, outdoor unit will remain
stop. If mixed with indoor unit cooling and heating, outdoor unit performs
heating operation.) When the setting is finished, the display is as below.
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
●
●
●
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
●
●
○
●
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
●
○
●
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
●
○
○
●
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
○
○
●
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
●
●
●
○
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
●
○
●
○
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
○
●
○
◇
○
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
○
●
○
◇
●
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
D805
(Green)
●
At shipment from
factory (default)
FILE NO. SVM-18020
-2
- 67 -