49
−
FILE NO. SVM-05016
8-4-4. Wiring connection
Fig. 8-4-5
<How to connect the connecting cable>
Wiring of the connecting cab
le can be carried out
without remo
ving of the fr
ont panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to local
cords) into pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N
·
m (0.12 kgfám).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Earth
line
Connecting cable
Cord clamp
Terminal block
Sc rew
Terminal
cover
Screw
Air Inlet grille
Front panel
CAUTION
•
Be sure to refer to the wiring system diagram
labeled inside the front panel.
•
Check local electrical cords and also any specific
wiring instructions or limitations.
Fig. 8-4-6
<Stripping length of connecting cable>
Fig. 8-4-7
NOTE
Use stranded wire only.
•
Wire type : More than 1.5 mm
2
(H07RN-F or
245 IEC66) or 1.3 mm
2
(AWG-16)
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (
i
mark)
located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
•
When attaching the air inlet grille, the contrary of
the removed operation is performed.
abou
t 15 c
m
Connecting cable
Earth line
50
40
10
10
2
1
Fig. 8-4-9