Unit model Indoor
RAS-18
N3KCV
Outdoor
RAS-18
N3ACV
Cooling capacity
(kW)
5.0
Cooling capacity range
(kW)
1.1-6.0
Power supply
Electric
Indoor
Operation mode
Cooling
characteristic Running current (A) 0.30-0.28
Power consumption
(W)
40
Power factor
(%)
60
Outdoor
Operation mode
Cooling
Running current (A) 6.38-5.85
Power consumption (W) 1380
Power factor (%) 98
Starting current (A) 6.68-6.13
COP 3.52
Operating Indoor High (dB-A) 44
noise (dB-A) 41
Medium (dB-A) 38
Low + (dB-A) 35
Low (dB-A) 32
Outdoor (dB-A) 49
Indoor unit Unit model
RAS-18
N3KCV
Dimension Height (mm) 320
Width (mm) 1050
Depth (mm) 243
Net weight (kg) 14
Fan motor output (W) 30
Air flow rate (High) (m3/min) 14.3
Outdoor unit Unit model
RAS-18
N3ACV
Dimension Height (mm) 550
Width
(mm)
780
Depth (mm) 290
Net weight (kg) 36
Compressor Motor output (W) 1100
Type
Twin rotary type with DC-inverter variable speed control
Model
DA131S1B-31FZ
Fan motor output (W) 43
Air flow rate (m3/min) 34.2
Piping Type Flare connection
connection Indoor unit Liquid side (mm)
∅
6.35
Gas side (mm)
∅
12.70
Outdoor unit Liquid side (mm)
∅
6.35
Gas side (mm)
∅
12.70
Maximum length (m) 20
Maximum chargeless length (m) 15
Maximum height difference (m) 10
Refrigerant Name of refrigerant R410A
Weight
(kg)
1.40
Wiring
Power supply
3Wires:includes earth(Outdoor)
connection Interconnection 4Wires:includes earth
Usable temperature range Indoor (°C) 21~32
Outdoor
(°C)
-10~46
Accessory
Indoor unit
Installation plate
1
Wireless remote controller 1
Batteries
2
Remote controller holder 1
Toshiba New IAQ filter 2
Mounting screw
6(
∅
4x25L)
Remote controller holder
Pan head wood screw
Installation manual 1
Owner's manual 1
* The specifications may be subject to change without notice for purpose of improvement.
2(
∅
3.1Lx16L)
–
4
–
2. SPECIFICATIONS
2-1. Specifications
1Ph/50hz/220-240V
1Ph/60hz/220-230V
FILE NO. SVM-12053