6

CAUTION

Refrigerant Piping Connection

1.  Cut the pipe with a pipe cutter.

2.  Insert a 

ß

 are nut into the pipe and 

ß

 are the pipe.

 

• 

Projection margin in 

ß

 aring : A (Unit : mm)

Rigid (clutch type)

Obliquity

Roughness

Warp

90

Imperial (wing nut type)

Outer dia. of copper pipe

R410A

6.35

1.5 to 2.0

9.52

1.5 to 2.0

12.70

2.0 to 2.5

Die

Pipe

A

Align the centers of the connecting pipes and tighten the 

ß

 are nut as far as pos-

sible with your 

Þ

 ngers. Then tighten the nut with a spanner and torque wrench 

as shown in the 

Þ

 gure.

     

Tightening connection

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

Ø6.35 mm

16 to 18 (1.6 to 1.8 kgf·m)

Ø9.52 mm

30 to 42 (3.0 to 4.2 kgf·m)

Ø12.70 mm

50 to 62 (5.0 to 6.2 kgf·m)

Evacuating

After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.

AIR PURGE

Evacuate  the  air  in  the  connecting  pipes  and  in  the  indoor  unit  using  a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

Outer dia.

of copper pipe

R410A tool used

Conventional tool 

used

6.35

0 to 0.5

1.0 to 1.5

9.52

0 to 0.5

1.0 to 1.5

12.70

0 to 0.5

1.0 to 1.5

Use a wrench to secure.

Use a torque wrench to tighten.

Flare nut

Half union

Internally
threaded side

Externally
threaded side

• 

Tightening torque of 

ß

 are pipe connections

Flare at
indoor unit side

Flare at
outdoor unit side

 

The operating pressure of R410A 
is higher than that of R22 (approx. 
1.6 times). It is therefore necessary 
to 

Þ

 rmly tighten the 

ß

 are pipe 

connecting sections (which connect 
the indoor and outdoor units) up to the 
speci

Þ

 ed tightening torque. Incorrect 

connections may cause not only a 
gas leakage, but also damage to the 
refrigeration cycle.

1.  How to shape the pipes 
 

Shape the pipes along the incused line on 
the outdoor unit.

2.  How to 

Þ

 t position of the pipes

 

Put the edges of the pipes to the place with 
a distance of 85 mm from the incused line.

     Shaping pipes

Incused line

     Flaring

Be sure to use a vacuum pump with counter-

ß

 ow prevention function so that 

inside oil of the pump does not 

ß

 ow backward into pipes of the air conditioner 

when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R410A, 
refrigeration cycle trouble may result.)
1.  Connect the charge hose from the manifold valve to the service port of the 

packed valve at gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4.  Operate  the  vacuum  pump  to  start  evacuating.  Perform  evacuating  for 

about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) 
(assuming  a  pump  capacity  of  27  liters  per  minute)  Then  con

Þ

 rm  that  the 

compound pressure gauge reading is –101 kPa (–76 cmHg).

5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.

     Using a vacuum pump

Packed valve at liquid side

Service port (Valve core (Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-

ß

 ow prevention

(For R410A only)

Charge hose
(For R410A only)

Handle Hi
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Lo

Charge hose 
(For R410A only)

Connecting pipe

–101 kPa

(–76 cmHg)

•  Open  the  valve  stem  all  the  way  out,  but  do  not  try  to  open  it  beyond  the 

stopper.

•  Securely tighten the valve stem cap with torque in the following table:

     Packed valve handling precautions

m

m

 

4

The hexagon wrench
is required.

Gas side
(Ø12.70 mm)

50 to 62 N·m
(5.0 to 6.2 kgf·m)

Gas side
(Ø9.52 mm)

30 to 42 N·m
(3.0 to 4.2 kgf·m)

Liquid side
(Ø6.35 mm)

16 to 18 N·m
(1.6 to 1.8 kgf·m)

Service port

9 to 10 N·m
(0.9 to 1.0 kgf·m)

• 

KEEP IMPORTANT 4 POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).

CAUTION

Wiring Connection

1.  Remove the valve cover from the outdoor unit.
2.  Connect  the  connecting  cable  to  the  terminals  as  identi

Þ

 ed  with  their 

respective matched numbers on the terminal block of indoor and outdoor 
unit.

3.  When connecting the connecting cable to the outdoor unit terminals, make 

a  loop  as  shown  in  the  installation  diagram  of  indoor  and  outdoor  unit  to 
prevent water coming in the outdoor unit.

4.  Insulate  the  unused  cords  (conductors)  from  any  water  coming  in  the 

outdoor unit. Proceed them so that they do not touch any electrical or metal 
parts.

1110251155-EN.indd   6

12/18/07   3:47:28 PM

Summary of Contents for RAS-16 SKV Series

Page 1: ...ies AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ESKY PУCСКИЙ HRVATSKI MAGYAR TÜRKÇE NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂN БЪЛГАРСКИ EESTI LATVISKI SLOVEN INA SLOVENŠ INA Cover indd 8 08 3 55 55 PM ...

Page 2: ...de Gás 7 DeÞnição do interruptor do telecomando 7 Selecção A B do telecomando 7 Execução do Teste 7 DeÞnindo de Reiniciação Automática 7 PT SPIS TRE CI ZASADY BEZPIECZE STWA SCHEMAT INSTALACYJNY URZ DZENIA WEWN TRZNEGO I ZEWN TRZNEGO 2 Dodatkowe Cz ci Instalacyjne 2 URZ DZENIE WEWN TRZNE 3 Miejsce Instalacji 3 Wycinanie Otworu oraz Monta P yty Instalacyjnej 3 Prace Elektryczne 3 Pod czenie Okablow...

Page 3: ...cul de instalare 3 Executarea unei g6uri 4i montarea pl6cii de instalare 3 Lucr6rile electrice 3 Racordarea cablurilor 4 Instalarea 5evilor 4i a furtunului de evacuare 4 Fixarea unit65ii interioare 5 Evacuarea 5 UNITATEA EXTERIOAR 5 Locul de instalare 5 Racordarea 5evilor de lichid refrigerent 6 Evacuarea 6 Racordarea cablurilor 6 ALTELE 7 VeriÞ carea scurgerilor de gaz 7 Setarea butonului selecto...

Page 4: ...ensure that water or dust does not enter Moreover do not use any existing piping as its pressure withstand may be insufÞcient and may contain impurities FOR USE BY QUALIFIED PERSONS ONLY TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK MAKE SURE ALL POWER SWITCHES ARE OFF FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK CONNECT THE CONNECTING CABLE CORRECTLY IF THE CONNECTING CABLE IS CON...

Page 5: ...peration For the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Batteries Pan head ...

Page 6: ...nd outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e c e p t i o n r a n g e Remote control Remote control...

Page 7: ...ont panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool Slit Slit Left hand connection with piping Bend the connecting pipe so that it is laid within 43 mm above the wall sur face If the connecting pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring be...

Page 8: ...oor side 50 mm or more Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch Do not form the drain hose into a wavy shape Do not rise the drain hose Extension drain hose Inside the room Drain hose Shield pipe Arrange the drain pipe for proper drainage from the unit Improper drainage can result in dew dropping Wall Drain guide Space for pipes This air conditio...

Page 9: ...of the vacuum pump enters the air conditioner which use R410A refrigeration cycle trouble may result 1 Connect the charge hose from the manifold valve to the service port of the packed valve at gas side 2 Connect the charge hose to the port of the vacuum pump 3 Open fully the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for a...

Page 10: ... leak with a gas leak detector or soap water This product is designed so that after a power failure it can restart automatically in the same operating mode as before the power failure Press and hold the RESET button for about 3 seconds After 3 seconds the electronic beeper makes three short beeps to tell you the Auto Restart has been selected To cancel the Auto Restart follow the steps described i...

Reviews: